Bakers Pride Oven FH-28 Ventilation Hood User Manual


 
Ventless Hood System Installation
13
Fire Extinguishing System
In the event of an appliance fire, serious injury, property damage or death could
occur if any part of the appliance obstructs the spray nozzles. Ensure that lids
and/or other parts of the appliance do not obstruct the spray pattern of either
nozzle.
The fire extinguishing system components used in this hood have been evaluated
by U.L. in the course of their classification for use on this hood.
An authorized Range Guard distributor must install and activate the filter hood
fire extinguishing system. To locate an authorized Range Guard Distributor use
the following contact information:
Ronald Woodward
Technical Service Specialist
Badger Fire Protection
4251 Seminole Trail
Charlottesville Va. 22911
Office: 800-446-3857 ext. 111
Fax: 434-974-4113
Mobile: 434-981-0505
1. After the hood has been properly secured to prevent movement, locate the end-of-line remote pull
station (at a point of egress or exit) in a manner approved by the local authority and in
accordance with applicable codes. To install the end-of-line remote, use ½” EMT and Range
Guard corner pulleys #97915.
2. Install two UL Listed; type “A”, 165 F. fusible links (load rating 3-45 lbs.) in the two appliance
detector positions (one in front of the grease baffle, one behind the grease baffle).
FUSIBLE
LINKS