Rosemount Raptor
5-36
Section 5. Installing a Raptor Level Gauging System
Figure 5-7. The same Level
addresses must be configured in
the Slave Database and the
Tank Database
The 2410 Temp Modbus addresses in the 2160 FCU Slave Database must be
equal to the ATD Modbus addresses in the 2410 Tank Database.
In this example the 2410 Temp Modbus Addresses for the three tanks are
entered in positions 1B, 2B, and 3B in the 2160 FCU Slave Database and in
tank positions 1, 2, and 3 in the 2410 Tank Database as illustrated in
Figure 5-8:
Figure 5-8. The same Modbus
addresses must be configured
for the ATD devices in the 2410
Tank Database and the 2410
Temp devices in the 2160 Slave
Database
Note that in the 2410 Tank Database the Modbus address of the 2410 itself is
automatically assigned to the ATD Modbus address for tank position 1.
2410 TANK DATABASE 2160 FCU SLAVE DATABASE
2410 TANK DATABASE 2160 FCU SLAVE DATABASE