Greenheck Fan SMD-201 Ventilation Hood User Manual


 
Model SMD-201 meets the requirements for smoke
dampers established by:
National Fire Protection Association
NFPA Standards 92A, 92B, 101 & 105
IBC International Building Codes
New York City (MEA listing #260-91-M)
CSFM California State Fire Marshal
Leakage (Smoke) Damper Listing (#3230-0981:104)
Application
Model SMD-201 is a leakage rated smoke damper with 3V style
blades. The SMD-201 has been qualified to 2,000 fpm (10.2 m/s) and
4 in. wg (1 kPa) for operational closure in emergency smoke control
situations. Model SMD-201 may be installed vertically (with blades run-
ning horizontally) or horizontally and is rated for airflow and leakage in
either direction.
Ratings
Leakage: UL 555S leakage class I
(to 6 in. wg [1.5 kPa] ).Leakage rated
in both directions
Pressure: 4 in. wg (1 kPa) - differential pressure.
Consult factory for sizes available in
6 in. wg (1.5 kPa).
Velocity: Operational rated to 2000 fpm
(10.2 m/s). Rating is for airflow in
either direction through damper.
Temperature: 350°F (177°C) depending on the
actuator
Standard Construction
Frame: 5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile
head and sill are used on sizes less
than 17 in. (432mm) high to maximize
free area and performance.
Blades: 16 ga. (1.5mm) galvanized steel,
reinforced with 3 longitudinal
structurally designed vee’s.
Seals: Flexible stainless steel jamb seals.
Extruded silicone rubber blade seals
Linkage: Concealed in jamb.
Axles:
1
2 in. (13mm) dia. plated steel
Bearings: Bronze sleeve type
Size Limitations
Minimum Size:
8 in. W x 6 in. H
(203mm W x 152mm H)
Maximum Size:
Single Section - 32 in. W x 50 in. H
(813mm W x 1270mm H)
36 in. W x 48 in. H
(914mm W x 1219mm H)
Multiple Section - 144 in. W x 100 in. H
(3658mm W x 2540mm H)
288 in. W x 50 in. H
(7315 mm W x 1270mm H)
Optional Features
• Galvanized steel sleeves.
• Stainless steel bearings
• OCI (Open closed indication switches)
Electric or pneumatic actuators to accomplish smoke
management and system functions.
• Transitions (R, C, O)
• POC retaining angles
• Momentary Switch
• Smoke detectors
• Sealed transition and sleeves
• Fail Open
Model SMD-201
Smoke Dampers
Steel 3V Blades
UL 555S Leakage Class I
H*
W*
LH
RH
“UL CLASSIFIED (see complete marking on
product)”
“UL CLASSIFIED to Canadian safety standards
(see complete marking on product)”
Standard 555S (Listing #R13317)
* W&H dimensions furnished approximately
1
/4 in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
R
Greenheck Fan Corporation certies that the
model SMD-201 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certied Ratings
Programs. The AMCA Certied Ratings Seal
applies to air performance ratings only.
Installation instruction available at www.greenheck.com