Thermal Max Detector
4351E
Description
The Thermal Max Detector 4351E recognises a maxi-
mum temperature of 78°C as sign of fi re. It complies
with Class BS and can be used up to a room height
of 6m.
Addressable conventional technology is used for alarm
transmission to the fi re detection control panel. The
detector addressing can be achieved in 2 ways:
A detector with an Address Module NG58-1 can be
individually identifi ed by the suitable control panel.
An address, which has been stored in the detector
by means of the Remote Programming and Test Unit,
is displayed on the Zonal Display Unit S300ZDU.
A test activation of the detector can be carried out
using the Remote Test Unit ECO1000RTU. In addition
to the test activation of the detector, the Remote Pro-
gramming and Test Unit S300RPTU can also be used
to set and display the following detector parameters:
• the detector address, and
• the date of the previous maintenance.
The detector can be attached to various detector ba-
ses and it can be protected against theft.
Addressable conventional technology
Alarm temperature 78°C
Addressing by means of address
module or detector parameterisation
Remote readout of detector condition
Function testable with Remote Test
Unit ECO1000RTU
Specifi cations
Operating voltage Supply through the detector line voltage
Current consumption typ. 85µA (quiescent)
Alarm temperature 78°C
Ambient temperature -30°C to +70°C (continuous operation)
Relative humidity 5 – 95% (no condensation)
Dimensions ø × H 102 × 43 (mm)
Colour cream
Weight 75g
Approval VdS G202016
Order number 242041
Order name Thermal Max Detector/Conv./300/SS 4351E