LST AD-58000-400 Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
AD-58000-400_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Thermal Detector
AD-58000-400
ADM loop technology with
Apollo/Discovery protocol
For use as maximum heat or
rate-of-rise heat detector
5 different operating modes
selectable
Optional connection of remote
indicator
Sealed electronics
Description
The addressable Thermal Detector AD-58000-400 is
based on the heat principle and was developed for the
indoor temperature supervision in a wide range of fi re
detection applications.
Depending on the parameter setup in the fi re detection
control panel, the detector operates either as maximum
heat detector with an alarm temperature of 61°C (EN
54-5 Class A2S) or 90°C (EN 54-5 Class CS), or as
rate-of-rise heat detector with a maximum temperature
of 58°C (EN 54-5 Class A1R), 61°C (EN 54-5 Class A2)
or 90°C (EN 54-5 Class CR). In Class A1R the detector
can be used up to a room height of 7.5m, in the other
operating modes a room height of 6m is permissible.
The proven ADM loop technology with Apollo/Discovery
protocol establishes a permanent communication bet-
ween the fi re detection control panel and the detector.
That ensures a periodical function testing of the detec-
tor. Fires are safely detected in the control panel by
continuously analysing the measured values.
The two LEDs with 360° visibility indicate the activated
condition of the detector. The detector address is se-
lected by means of a code card in the detector base.
Therefore the detector can be changed without additi-
onal tools.
The detector can be attached to various bases and it
can be protected against theft.