LST AW-55000-420 Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
AW-55000-420_DBL_LST_EN_0804.PDF • PAGE 1
ABuilding Safety. Building Security.
Thermal Detector
AW-55000-420
ADM loop technology with
Apollo/Discovery protocol
For use as maximum heat or
rate-of-rise heat detector
Alarm temperature 55°C
Optional connection of remote
indicator
Sealed electronics
Description
The addressable Thermal Detector AW-55000-420 is
based on the heat principle and was developed for the
indoor temperature supervision in a wide range of fi re
detection applications.
The detector is assigned to class A2S and A2R and can
be used up to a room height of 6m. Depending on the
parameter setup in the fi re detection control panel, the
detector can operate either as maximum heat detector
with an alarm temperature of 55°C, or as rate-of-rise
heat detector with a maximum temperature of 55°C.
The proven ADM loop technology with Apollo/Discovery
protocol establishes a permanent communication bet-
ween the fi re detection control panel and the detector.
That ensures a periodical function testing of the detec-
tor. Fires are safely detected in the control panel by
continuously analysing the measured values.
The activated condition of the detector is indicated by a
red LED. The detector address is selected by means of
a code card in the detector base. Therefore the detec-
tor can be changed without additional tools.
The detector can be attached to various bases and it
can be protected against theft.
Specifi cations
Operating voltage Supply through loop voltage
Current consumption max. 250µA (quiescent)
Ambient temperature -20°C to +70°C
Relative humidity 0 – 95% (no condensation)
Dimensions ø × H 100 × 42 (mm)
Colour white
Weight 105g
Approval VdS G294029
Order number 242023
Order name Thermal Detector/Anal./XP95/Apo AW-55000-420