(Conforming standard UL 508C, CSA C22.2 No.14)
(1) Installation
This inverter is a UL / cUL Listed, enclosed type device with a suitably rated enclosure.
Design an enclosure so that the inverter surrounding air temperature, humidity and atmosphere satisfy the
specifications.
(Refer to page 152.)
Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power OFF, wait for more
than 10 minutes, and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of
electrical shock.
Wiring protection
For installation in the United States, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses or UL
489 Molded Case Circuit Breaker (MCCB) must be provided, in accordance with the National Electrical Code and any
applicable local codes.
For installation in Canada, Class RK5, Class J, Class CC, Class L, Class T or any faster acting fuses or UL 489 Molded
Case Circuit Breaker (MCCB) must be provided, in accordance with the Canada Electrical Code and any applicable
provincial codes.
* Maximum allowable rating by US National Electrical Code.
Exact size must be chosen for each installation.
Appendix 3 Instructions for UL and cUL compliance
FR-F720P-K
0.75
1.5 2.2 3.7 5.5 7.5 11 15
18.5
22 30 37 45 55
Rated fuse voltage(V) 240V or more
Fuse
maximum
allowable
rating (A)*
Without power factor
improving reactor
15 20 30 40 60 80 150 175 200 225 300 350 400 500
With power factor
improving reactor
15 20 20 30 50 70 125 150 200 200 250 300 350 400
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
15 15 20 35 50 70 100 125 175 200 250 350 400 500
FR-F720P-K
75
90 110
Rated fuse voltage(V) 240V or more
Fuse
maximum
allowable
rating (A)*
Without power factor
improving reactor
⎯⎯⎯
With power factor
improving reactor
500 600 700
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
700 800
1000
FR-F740P-K
0.75
1.5 2.2 3.7 5.5 7.5 11 15
18.5
22 30 37 45 55
Rated fuse voltage(V) 480V or more
Fuse
maximum
allowable
rating (A)*
Without power factor
improving reactor
6 10 15 20 30 40 70 80 90 110 150 175 200 250
With power factor
improving reactor
6 10 10 15 25 35 60 70 90 100 125 150 175 200
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
15 15 15 15 25 40 50 70 80 100 125 175 200 250
FR-F740P-K
75
90 110 132 160 185 220 250 280 315 355 400 450 500 560
Rated fuse voltage(V) 500V or more
Fuse
maximum
allowable
rating (A)*
Without power factor
improving reactor
⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯⎯
With power factor
improving reactor
250 300 350 400 500 600 700 800 900 1000 1100 1200 1350 1500 1800
Molded case circuit breaker
(MCCB)
Maximum allowable rating (A)*
350 450 500 650 800 800 1000 1200 1200 1200 1600 1600 2000 2000 2500