Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-off
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than
1/2 PSIG (3.5 kPa).
This appliance, as well as its individual shut-off valve,
must be disconnected from the gas supply piping sys-
tem during any pressure testing of the system at test
pressures in excess of 1/2 PSIG (3.5 kPa).
When checking appliance regulator function, make
certain pressure of natural gas supply is between 6
and 14 inches of water column or, if converted for LP
gas, between 11 and 14 inches.
THE PRESSURE TESTING SHOULD BE PER-
FORMED BY MEANS OF THE INJECTOR THREAD
ZONE
Figure 13.
Pressure Test Method
x Remove grate and burner cap
x Remove aluminum gas spreader
x Temporarily remove the injectors
x Connect the pressure Test instrument into injector
holder thread zone (M6x0,75)
x Check if the cooktop has the correct pressure
x Fix the injector removed for testing and replace
the parts in the right position.
1
Gas test inlet
Thread