Whirlpool RJH 3330-1 Ventilation Hood User Manual


 
READ AND SAVE THESE INSTRUCTIONS
YLrlmml
NOTE: The fan in the Microshelf Hood turns on
automatically to protect the microwave oven
when the temperature inside the hoodreaches
122°F (SO’C). It turns off automatically when
the temperature falls below 95°F (35°C).
I. INSTALLATION REQUIREMENTS
A. Space Requirements
1 CORPORATION
INSTALLATION
AND
OPERATING
INSTRUCTIONS
FOR
MICROSHELF HOOD
MODEL RJH 3330-l
Before you begin,
read the following instructions
completely and carefully. If followed, they will simplify
the installation job.
IMPORTANT: OBSERVE ALL GOVERNING CODES
AND ORDINANCES
SAVE THESE INSTRUCTIONS FOR THE LOCAL
ELECTRICAL INSPECTOR’S USE
BEFORE YOU USE YOUR MICROSHELF HOOD:
Be sure your Microshelf Hood is installed on an
appropriate wall strong enough tosupport this appliance.
NOTE: The shelf of the Microshelf Hood is designed
to support a Microwave Oven with a net
weight of up to 75 pounds.
The area used for the installation must be suitable forthe
size, function, and protection (from elements) of the
Microshelf Hood.
CAUTION: When mounting the Microshelf Hood to a
wall, you must locate 2 studs in the wall.
Do not attempt to install the hood if the 2
wall studs are not found.
Be careful when drilling holes into a wall. Electrical wires
and water pipes may be concealed behind the wall
covering.
APPROVED FOR USE WITH WHIRLPOOL RJM
AND RHM SERIES AND THE RFM 7300-l
MICROWAVE OVENS.
APPROVED FOR USE OVER WHIRLPOOL
CONVENTIONAL RANGE COOKTOPS THAT DO
NOT HAVE A GRILLE.
Page 1
A typical installation can be seen in Figure 1. Study
Figure 1 before proceeding. The Microshelf Hood
requires an opening that is 30” wide. It is
recommended that the cabinet above the cooktop
be a maximum of 15” high. This provides adequate
space between the range cooktop and the
Microshelf Hood.
l-
CEILING --(
APPROX 96”
%I
FROM FLOOR
FURR DOWN
FLOOR
T
MICROWAVE
OVEN
t u
SHELF1
n000
I5”MIN
COOK TOP?
Figure 1
F
3;‘. IO”
1 DUCT
%
TRANSITION
DUCT
PROVIDED
WITH HOOD
II
$ THICK
SHEET ROCK
B. Electrical Requirements
A 120 Volt, 60 Hz, AC only, 20 Ampere fused
electrical supply is required (time delay fuse or
circuit breaker is recommended). It is
recommended that a separate circuit serving only
this appliance be provided.
C. Venting Requirements
For vented installations, the venting system must
terminate to the outside.
CAUTION: Do not terminate the vent in an attic or
other enclosed space. This type of installation may
result in a fire.
If a vertical venting system is used, using 3%” x 10”
duct, the maximum length allowed is 25 feet. If
elbows are used in the venting system, reduce the
length of 3%” by 10” duct by 24 feet for each elbow
used.
The Microshelf Hood may be centered horizontally
as shown in Figure 2. The maximum length of duct
run horizontally, using one 3%” x 10” elbow, is one
foot