304 AISI WALL TYPE HOODS
SUPERTREDIL - S line - 1100mm
Net weight - kg. 90 111 130 154 176 197 219 240
Inlet Air Capacity - mc/h 1110 1470 1830 2220 2580 2940 3330 3690
Air Capacity - mc/h 1500 2000 2500 3000 3400 3900 4400 4900
height 500 500 500 500 500 500 500 500
depth 1100 1100 1100 1100 1100 1100 1100 1100
width 1200 1600 2000 2400 2800 3200 3600 4000
External dimensions - mm
STPF1112
641249
STPF1116
641250
STPF1120
641251
STPF1124
641252
STPF1128
641253
STPF1132
641254
STPF1136
641255
STPF1140
641256
CHARACTERISTICS MODELS
TECHNICAL DATA
RANGE
COMPOSITION
A range of hoods exploiting the
"inductive emission" principle.
Untreated air is introduced inside to
partly compensate for that removed.
This results in better drawing of
fumes towards the filter surface and
reduced air-treatment costs. The
range consists of hoods with 8
different lengths (1200. 1600, 2000,
2400, 2800, 3200, 3600 and 4000
mm) and 1100 mm deep.
FUNCTIONAL AND
CONSTRUCTION
FEATURES
Constructed entirely in 304 AISI
stainless steel.
Two separate air circuits
(extraction and intake) to reduce the
quantity of treated air released in the
environment.
Rear exhaust with filters and front
air intake through a narrow slot sized
to obtain the correct induction effect.
Perforated panel inside the intake
circuit to guarantee a perfect and
uniform air distribution.
Completely insulated intake area
to avoid external condensation.
Labyrinth filters in 304 AISI
stainless steel easily removable for
cleaning. Labyrinth filters guarantee
constant filtration to avoid clogging
and protect against fire.
Perimetral gutter with drain hole to
transfer grease into a 304 AISI
container.
External panels with upturned
edges to avoid injuries.
The outlet holes are sized in order
to minimize drops in pressure.
Pressure gauging for perfect
calibration.
Built-in lighting with protective
screen.
Available, as optional accessory,
an air intake Plenum, which is
insulated to avoid condensation.
Heating and air conditioning costs
reduced up to 60%.