American Aldes HRV 700SFD Ventilation Hood User Manual


 
PRODUCT
SPECIFICATIONS
AND ENGINEERING
INFORMATION
-----
SUBMITTAL DATA
460 - 0403
Standard Damper
Defrost
GENERAL FEATURES
Thermally conductive aluminum heat exchange core, cross-
flow design, easily removed for cleaning or service.
Insulated 20 gauge white powder coated galvanized steel
cabinet.
Direct drive centrifugal forward curve blowers, Multi-speed
providing 600 to 1100 cfm. one in each air stream.
Two efficient three speed PSC double shafted motors 120 V,
4 Amps each (8.1 Amps total on high speed),
1 ph. 1/4HP, 1625 RPM. Watts - total on high speed - 972.
Washable filters, one in each air stream protect the core. Easy
to access and clean.
Installation accessories and controls make installation simple.
ALDES Pool Model Heat Re-
cover Ventilators are designed
to exhaust humid air from indoor
swimming pools and spa area
and to supply tempered fresh air
from outdoors. It incorporates
an efficient aluminum core for
heat recovery of waste heat to
temper the fresh outdoor air, to
provide and economical solu-
tion to excessive humidity, odor,
stuffiness, and other indoor air
pollutants. The model
P1200SDD is intended for small
commercial, institutional, and
residential applications for pool
and wetted deck areas up to
1000 square feet.
The pool model has three modes
of operation to meet the unique
needs of pools. The normal
ventilation mode provides ex-
haust of humid air and supply of
fresh outdoor air, with heat re-
covery in the efficient aluminum
cores. This mode is controlled
by an adjustable dehumidistat
that opens the fresh air damper
to the outdoor air intake, and
operates both the supply and
exhaust fans. (A duct heater or
hot water coil may be installed in
the supply duct to provide addi-
tional heat to the incoming air or
recirculating air. This heater
would be controlled by a duct
mounted thermostat.)
The second mode of operation
occurs when the humidity level
falls below the setpoint of the
dehumidistat. The exhaust fan
shuts off, the supply air damper
closes off outdoor air, and opens
The third mode of operation pro-
vides automatic defrost by shut-
ting off fresh air intake in a cycle
of 4.5 minutes off, 17 minutes
on. The defrost cycle occurs
when outdoor temperatures are
below 27°F (-3°C)
the recirculation air circuit. This
mode maintains constant air cir-
culation in the conditioned space,
and a means of heating the con-
ditioned space if a duct heater or
hot water coil is installed in the
supply duct.
HRV P1200SDDHRV P1200SDD
HRV P1200SDDHRV P1200SDD
HRV P1200SDD
HEAHEA
HEAHEA
HEA
T RECOVERY VENTILAT RECOVERY VENTILA
T RECOVERY VENTILAT RECOVERY VENTILA
T RECOVERY VENTILA
TT
TT
T
OROR
OROR
OR
POOL MODELPOOL MODEL
POOL MODELPOOL MODEL
POOL MODEL
ALDES HRV P1200SDD
Heat Recovery Ventilator
for Swimming Pools
PART NO. 28 111