Chilled Water Performance Specifications 8.9°C (48°F) EWT
(
Temperature dry bulb
(DB), wet bulb (WB)
°C (°F)
CW Delta T
°C (°F)
Total Net
Capacity
kW (BTU/hr)
Sensible Net
Capacity
kW (BTU/hr)
Sensible Heat
Ratio
SHR
CW Flow Rate
l/s (GPM)
Total CW Pressure
Drop
kPa (ft H
2
O)*
26.7°C DB, 17.1°C WB (80°F DB, 62.8°F WB)
5.5 (10) 35.7 (122,000) 34.6 (118,000) 0.97 1.6 (25.5) 63 (21.3)
6.6 (12) 32.9 (112,000) 31.9 (109,000) 0.97 1.2 (19.7) 39 (12.9)
7.7 (14) 30.3 (103,000) 29.4 (100,000) 0.97 1.0 (15.7) 25 (8.3)
8.8 (16) 27.7 (95,000) 26.9 (92,000) 0.97 0.8 (12.7) 17 (5.5)
10 (18) 25.3 (86,000) 24.5 (84,000) 0.97 0.7 (10.4) 11 (3.9)
11.1 (20) 22.7 (78,000) 22.3 (76,000) 0.98 0.5 (8.5) 8 (2.5)
29.4°C DB, 18.1°C WB (85°F DB, 64.5°F WB)
5.5 (10) 42.3 (145,000) 41.5 (142,000) 0.98 1.9 (29.9) 86 (28.9)
6.6 (12) 39.4 (134,000) 38.6 (132,000) 0.98 1.5 (23.3) 53 (17.8)
7.7 (14) 36.5 (125,000) 35.8 (122,000) 0.98 1.2 (18.6) 35 (11.6)
8.8 (16) 33.7 (115,000) 33.1 (113,000) 0.98 1.0 (15.1) 23 (7.9)
10 (18) 31.1 (106,000) 30.4 (104,000) 0.98 0.8 (12.5) 16 (5.3)
11.1 (20) 28.5 (97,000) 27.9 (95,000) 0.98 0.7 (10.4) 12 (3.9)
32.2°C DB, 18.9°C WB (90°F DB, 66.1°F WB)
6.6 (12) 47.0 (161,000) 46.1 (157,000) 0.98 1.7 (27.5) 73 (24.5)
7.7 (14) 43.9 (150,000) 43.0 (147,000) 0.98 1.4 (22.1) 48 (16.2)
8.8 (16) 40.9 (140,000) 40.1 (137,000) 0.98 1.1 (18.1) 33 (10.9)
10 (18) 37.6 (128,000) 37.2 (127,000) 0.99 0.9 (14.9) 23 (7.6)
11.1 (20) 34.8 (119,000) 34.4 (118,000) 0.99 0.8 (12.5) 16 (5.3)
35.0°C DB, 19.8°C WB (95°F DB, 67.7°F WB)
7.7 (14) 51.4 (176,000) 50.9 (174,000) 0.99 1.6 (25.6) 64 (21.5)
8.8 (16) 48.2 (165,000) 47.7 (163,000) 0.99 1.3 (21.1) 44 (14.8)
10 (18) 45.0 (154,000) 44.6 (152,000) 0.99 1.1 (17.6) 31 (10.4)
11.1 (20) 42.0 (143,000) 41.6 (142,000) 0.99 0.9 (14.8) 22 (7.6)
37.8°C DB, 20.7°C WB (100°F DB, 69.2°F WB)
7.7 (14) 60.0 (205,000) 59.4 (203,000) 0.99 1.9 (29.7) 85 (28.6)
8.8 (16) 56.0 (191,000) 56.0 (191,000 1.00 1.5 (24.3) 58 (19.4)
10 (18) 52.6 (180,000) 52.6 (180,000 1.00 1.3 (20.4) 41 (13.9)
11.1 (20) 49.4 (169,000) 49.4 (169,000) 1.00 1.1 (17.3) 30 (9.9)
40.6°C DB, 21.6°C WB (105°F DB, 70.8°F WB)
7.7 (14) 68.6 (234,000) 68.6 (234,000) 1.00 2.1 (33.7) 109 (36.5)
8.8 (16) 64.9 (222,000) 64.9 (222,000) 1.00 1.8 (28.0) 76 (25.4)
10 (18) 61.3 (209,000) 61.3 (209,000) 1.00 1.5 (23.5) 54 (18.2)
Note: All values are accurate to +/- 5% and based on full speed with standard filters.
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
Note: Any CW flow rate of 0.19 l/s - 0.32 l/s (3.0 GPM - 5.0 GPM) may cause an increased error in flow rate and power calculation. A
fluid flow fault may result. Any flow rate under 0.19 l/s (3.0 GPM) may also display as 0 in the flow rate and power calculation.
Note: For sustained operation, a maximimum flow rate of 2.2 l/s (34 GPM) is recommended. This may be exceeded by 25% for peak
conditions.
* To convert feet of water to PSIG, use the following formula: ft H
2
O ÷ 2.307 = PSIG.