25InRow RP Technical Data Manual
Air-cooled Data - General
Note: Reduce airflow and cooling capacity specifications by 7% for cooling units run at low input voltage (380 V).
MODEL ACRP 100 Series
AIR SYSTEM - FAN (Standard Filter Installed)
Air Volume - l/s (SCFM) 2265 (4800)
Fan Motor - W (HP) 1100 (1.5)
Number of Fans 2
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
(ft
2
)
.56 (6.0)
Rows Deep 4
HUMIDIFICATION - SOLID STATE ELECTRODE CANISTER
Flush Cycle automatic
Capacity - kg/hr (lbs/hr) 3 (6.6)
kW 2.25
REHEAT
Electric - Equally Loaded Two Stage, Finned Tubular, Low-Watt Density
Capacity - kW (BTU/hr) 6 (20,500)
Stages 2
FILTERS - PLEATED (STANDARD)
Quantity 3
Size - mm (in) 418 x 470 (16.45 x 18.5)
Depth - mm (in) 96 (3.78)
Efficiency (%) 30
FILTERS - PLEATED (OPTIONAL)
Quantity 3
Size - mm (in) 418 x 470 (16.45 x 18.5)
Depth - mm (in) 96 (3.78)
Efficiency (%) 85
PHYSICAL DATA
Weight - kg (lbs) 378 (833)
Height - mm (in) 1991 (78.40)
Width - mm (in) 600 (23.62)
Depth - mm (in) 1070 (42.13)
CONNECTION SIZES
Refrigerant
Discharge 7/8 in ODF brazed
Maximum pressure drop - bar (PSI) 0.7 (10)
Liquid 7/8 in ODF brazed
Humidifier
Supply Line - mm (in) 6.35 (1/4)
Condensate Drain
Drain Line - mm (in) 12.7 (1/2)