BEST BY BROAN P.O. BOX 140 HARTFORD, WISCONSIN 53027
L
L
C
A
2
"
3
16
A
KER222 SERIES WIRING KER222 SERIES MOUNTING
FRAMING BEHIND
WOOD CROSS
SUPPORT
WOOD CROSS
SUPPORT – SECURED
TO FRAMING AND
LOCATED BEHIND
DRYWALL
WIRING
BOX
AIR OUTLET Ø 7-7/8”
6-3/16”
DRYWALL
NOTE: Minimum hood distance above cooktop must not be less than 24”.
A maximum of 30” above the cooktop is highly recommended for best capture of cooking impurities.
Distances over 30” are at the installer and users’ discretion; and if ceiling height and flue length permit.
MOUNTING BRACKET LOCATION
(ABOVE 36” HIGH COOKTOP)
HOOD DIMENSION CEILING MOUNTING DISTANCE ABOVE 36” HIGH COOKTOP (SEE NOTE BELOW)
WIDTH A HEIGHT 24” 25” 26” 27” 28” 29” 30”
MOUNTING BRACKET LOCATION ABOVE 36” HIGH COOK TOP
8 FEET 29-13/16” 30-13/16” 31-13/16” 32-13/16” 33-13/16”
90cm 9-5/8” 9 FEET 31-13/16” 32-13/16” 33-13/16” 34-13/16” 35-13/16”
35-7/16”
10 FEET WITH 29-13/16” 30-13/16” 31-13/16” 32-13/16” 33-13/16” 34-13/16” 35-13/16”
FEXTK42
8 FEET 31-1/16” 32-1/16” 33-1/16” 34-1/16” 35-1/16”
42” 9-15/16” 9 FEET 33-1/16” 34-1/16” 35-1/16” 36-1/16” 37-1/16”
10 FEET WITH 31-1/16” 32-1/16” 33-1/16” 34-1/16” 35-1/16” 36-1/16” 37-1/16”
FEXTK42
8 FEET 31-9/16” 32-9/16” 33-9/16” 34-9/16” 35-9/16”
48” 8-7/8” 9 FEET 33-9/16” 34-9/16” 35-9/16” 36-9/16” 37-9/16”
10 FEET WITH 31-9/16” 32-9/16” 33-9/16” 34-9/16” 35-9/16” 36-9/16” 37-9/16”
FEXTK42