7
Total of above = 20 + 2.2 + 3 + 2.2 + 17 + 23 + 10 + 2.2 = 79.6 feet. Since each 10 feet
is equivalent to 1 psi pressure loss, 79.6 feet is equivalent to approximately 32 psi from
an original Boiler supply of 40 psi.
It is suggested that, wherever possible, the steam supply line to the appliance is a
separate line from the steam source. If the appliance must be supplied from a line
supplying other appliances, the pipe sizes and pressure will have to be verified. Further,
during idle periods, when the steam in the supply line is not in use, water will form from
condensed steam in the supply line. It is advisable to prevent water pockets from
forming in the steam line and impeding the steam flow when it is required. Therefore, the
steam supply line should be installed level or run slightly downwards towards the
appliance. Install a Ball Float Trap near the appliance to drain out water (condensed
steam) from the line to assure clean dry steam to the appliance.
INLET
TO HEAT
EXCHANGER
TO DRAIN
1
2
3