Bloomfield WVAE-30F Ventilation Hood User Manual


 
INSTALLATION (continued)
9
DANGER
BURN HAZARD
HOT OIL SPILL
Any additional remote pull
station must not be installed on
the front or sides of the fryer
forward of the ventilator side
panels.
Discharge of the fire
extinguishing system into hot
oil will cause hot foam to spill
over from the frypot.
Serious burns and other
injuries can result from contact
with hot oil and from slipping in
spilled oil.
Exclusive Anti-Fire System
In the unlikely event that both
the temperature control
thermostat and hi-limit detector
fail, and the oil temperature
climbs above the safety limit,
the fire suppression system will
discharge, cooling the oil below
the oil’s (approximately) 540ºF
auto-ignition temperature, and
preventing a fire from
occurring.
BACK, HORIZ.,
RIGHT SIDE
INSTALL (5-3/4”)
BACK, HORIZ.,
LEFT SIDE,
INSTALL (8-1/4”)
MANUAL PULL
STATION PIPING
INSTALL ON LEFT
SIDE OF HOOD
INSTALL ON RIGHT
SIDE OF HOOD
OR
SIDE, VERT. (6”)
SIDE, HORIZ.
(13-1/2”)
CENTER,
VERT. 3”
INSIDE OF HOOD
LOOKING UP
IMPORTANT!
VACUUM FITTING
DO NOT INSTALL
DISCHARGE NOZZLE
HERE!
280ºF
FUSIBLE LINK
DISCHARGE
NOZZLES
FRYPOT
FUSIBLE LINK
NOTE
CABLE
ROUTED
UNDER
GUIDE
CRIMP
FERRULE
450ºF
FUSIBLE
LINK
HEATSINK
CLIP
M381 301603 OpM (Supplemental) NFPA Hood