48
Table 2 — Electrical Data Without VAV Option
LEGEND
*Fused disconnect only.
†Exhaust and supply fan motors are 230-1-60.
UNIT SIZE
62M
VOLTAGE
(V-Ph-Hz)
ERV WHEEL
FLA
EXHAUST AND SUPPLY MOTOR
HEATER
SIZE
(kW)
POWER SUPPLY
PRE-HEATER
(Optional)
FLA
DISCONNECT
(Optional)
NEC - FLA Hp FLA MCA MOCP Amps
Fuse Size*
Amps
040
115-1-60 0.7 3.96
.6
— 9.27 9.90 12.87 — 30 12
2 26.64 31.64 31.64 17.39 40 30
230-1-60
0.3 1.74†
— 4.44 4.35 5.66 —
30
5
2 13.76 16.37 16.37 8.7 15
208/230-3-60
— 4.11 4.35 5.66 — 5
2 9.66 11.30 11.30 5.03 10
460-3-60
— 2.34 2.72 4.89 — 3
2 4.85 5.86 7.40 2.51 5
575-3-60
— 1.87 2.17 3.91 — 2
2 3.75 4.18 6.90 2.01 4
075
115-1-60 0.7 9.8
0.5
— 20.69 24.5 31.85 — 40 30
2 38.08 46.24 49.24 17.39 60 45
5 64.17 78.85 78.85 43.48 100 70
230-1-60
0.3
4.9
— 10.46 12.25 15.93 —
30
15
2 19.16 23.12 24.62 8.7 20
5 32.2 39.42 39.42 21.74 60 35
208/230-3-60 2.2
— 5.03 5.50 7.15 —
30
6
2 10.05 11.78 12.18 5.03 12
5 17.59 21.21 21.21 12.57 20
460-3-60 1.1
— 2.53 2.75 3.58 — 4
2 5.04 5.89 6.09 2.51 6
5 8.81 10.60 10.60 6.28 10
575-3-60 0.9
— 2.10 2.25 2.93 — 3
2 4.11 4.76 4.94 2.01 5
5 7.13 8.53 8.53 5.03 8
120
115-1-60 0.7 16
1
— 33.09 40.00 52.00 — 60 50
2 50.48 61.74 69.39 17.39 80 60
5 76.57 94.35 95.48 43.48 200 90
230-1-60
0.3
8
— 16.66 20.00 26.00 — 30 25
2 25.36 30.87 34.70 8.70 40 30
5 38.40 47.17 47.74 21.74 60 45
208/230-3-60 4.2
— 9.03 10.50 13.65 — 30 12
5 14.05 16.78 18.68 5.03 30 18
8 21.59 26.21 26.22 12.57 40 25
460-3-60 2.1
— 4.53 5.25 6.83 —
30
6
2 7.04 8.39 9.34 2.51 8
5 10.81 13.10 13.11 6.28 12
575-3-60 1.7
— 3.70 4.25 5.53 — 5
2 5.71 6.76 7.54 2.01 6
5 8.73 10.53 10.55 5.03 10
170
230-1-60
0.6
8
1
— 16.93 20.00 26.00 — 30 25
5 38.67 47.17 47.74 21.74 60 45
8 51.71 63.48 63.48 34.78 80 60
10 60.41 74.35 74.35 43.48 100 70
208/230-3-60 4.2
— 9.33 10.50 13.65 — 30 12
5 21.90 26.21 26.22 12.57 40 25
8 29.44 35.63 35.63 20.11 60 35
10 34.46 41.91 41.91 25.13 60 40
460-3-60 2.1
— 4.69 5.25 6.83 — 30 6
5 10.97 13.10 13.11 6.28 30 12
8 14.74 17.82 17.82 10.05 30 18
10 17.26 20.96 20.96 12.57 30 20
575-3-60 1.7
— 3.88 4.25 5.53 — 30 5
5 8.90 10.53 10.55 5.03 30 10
8 11.92 14.30 14.30 8.04 30 12
10 13.93 16.82 16.82 10.05 30 15
ERV — Energy Recovery Ventilator
FLA — Full Load Amps
Hp — Horsepower
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC — National Electric Code
N/A — Not Applicable