Carrier ERVCCSHB Ventilation Hood User Manual


 
3
MAINTENANCE
1. The motors are factory lubricated. Lubricating the bearings
is not recommended.
2. The core should be vacuumed every three months to
remove dust that would inhibit the energy transfer. Do not
use water. The core should only be serviced when the
outdoor temperature is between 60°F(16°C) and 75°F
(24°C) and dry.
NOTE: If the edges of the core are soft, do not try to service the
core. The air passages can be damaged and/or closed off by
handling it or trying to remove it.
3. A dirty air filter will cause excessive strain on the blower
motor. The filters in your ERV are washable and should be
cleaned every 3 months. Use a vacuum cleaner to remove
the heaviest portion of accumulated dust, then wash in
warm water.
NOTE: Do NOT clean these filters in a dishwasher or dry them
with heating appliances as they will be permanently damaged. Use
lukewarm water to clean filters. Replace filters only when they are
completely dry.
4. Regularly check the screen on the exterior intake hood and
clean as necessary.
BEFORE YOU REQUEST A SERVICE
CALL
S Check the main power disconnect switch. Verify that the circuit
breakers are ON or that fuses have not blown. If you must reset
breakersor replace fuses, do so only once. Contact your servicing
dealer for assistance if the breakers trip or the fuses blow a second
time.
S Check for sufficient airflow. Check air filters for accumulations of
large particles. Check for blocked exhaust--air grilles or ductwork.
Keep grilles and duct work open and unobstructed.
S Check to see if the unit is calling for air exchange, or unit is in
defrost. When outdoor ambient temperature is below 23°F
(--5°C), some degree of defrost mode is possible. Defrost length
could be 5 to 20 minutes, depending on temperature and settings.
IfyourERVstillfailsto operateproperly,contactyourservicingdeal-
er.Givehimyourmodelandserialnumber.Withthisinformation,the
dealer will be able to correct any problems.
DOOR IS
DETACHABLE
FILTERS ARE
REMOVABLE BY
PULLING STRAIGHT
OUT
ENERGY RECOVERY
CORE CAN BE REMOVED
BY PULLING STRAIGHT OUT
BRIEF CASE
TYPE LATCH
A99300
Fig. 4 -- Horizontal Application
ERV