Carrier HRVCCSHB1100 Ventilation Hood User Manual


 
10
If the integrated control LED of the unit is flashing, this means the unit sensors detected a problem. See the table below to know where on the
unit the problem occurs.
Table 5 – Troubleshooting
LED flashes GREEN. Thermistor error. Reference Table 6 for proper temperature vs. resistance relationship. If thermistor
is defective, replace the entire port assembly (fresh air from outside port).
LED flashes RED.
The door is open and the unit is not
unplugged.
Close the door and press once on the integrated control push button to reset the
unit.
Exhaust motor error. Go to Problem 5 below.
LED flashes AMBER. Damper error. Go to Problem 6 below.
Problem: Possible causes: You should try this:
1. Unit does not work. S The circuit board may be defective. S Unplug the unit. Disconnect the main
control and the optional control(s) (if need
be). Jump G and B terminals. Plug the unit
back and wait about 10 seconds. If the
motorsrunonhighspeedandthedamper
opens, the circuit board is not defective.
NO C NC I OC OL Y R G B
2. The damper actuator
does not work.
S The damper actuator or the integrated
damper port mechanism may be
defective.
S Unplugtheunit.Disconnectthemaincontroland theoptionalcontrols(s)(ifneed
be).Wait 10 seconds and plug the unit back. Check if the damper opens. If not,
use a multimeter and check for 24VAC on J12--1 and J12--2 (in electrical
compartment). If there is 24VAC, replace the entire port assembly.
NOTE: It is normal to experience a small delay (7--8 seconds) before detecting
the 24VAC signal at starting--up. This signal will stay during 17--18 seconds
before disappearing.
S The circuit board may be defective. S If there is no 24VAC, replace the circuit board.
3. The wall control does
not work OR its indi-
cator flashes.
S The wires may be in reverse position. S Ensure that the color coded wires have been connected to their work OR its
indicator flashes.appropriate places.
S The wires may be broken. S Inspectevery wire and replace any that are damaged.
S The wire in the wall OR the wall. S Remove the wall control and test it right beside the unit using another control
may be defective.shorter wire.If thewallcontrol works there, changethe wire.If
it doesnot, change the wall control.
4. The dehumidistat
does not work OR
the 20--minute. push--
button timer does not
work OR its indicator
light does not stay
on.
S The wires may be in reverse position. S Ensure that the color coded wires have been connected to their appropriate
places.
S The dehumidified or push button may be
defective.
S Jump the OL and OC terminals. If the unit
switch to high speed, remove the
dehumidistat orpush button and testit right
besidethe unitusing anothershorterwire.If
it works here, changethe wire. If it doesn’t,
change the dehumidistat or the push button.
NO C NC I OC OL Y R G B
5. The supply and/or
exhaust motor do not
work.
S The circuit board may be defective. S Press on the integrated control push button until the unit turn on low speed (the
LED will light AMBER). Using a multimeter, check the voltage on J4--1 and
J4--2 (for supply motor), and on J5--1 and J5--2 (for exhaust motor). The reading
must be ±68VAC. Then set the unit on high speed by pressingon theintegrated
control 1 more time (the LED will light GREEN).Using a multimeter, check the
voltage onJ4--1 andJ4--2 (for supply motor),and onJ5--1 andJ5--2 (for exhaust
motor).Thereading must be± 120VAC.Ifallthereadingscorrespondtotheright
voltage values, the circuit board is not defective. If one or both readings are
different, changethe circuit board.
S The motor(s)may be defective. S Using a multimeter, check the ohms value on each motor connectors. Black
motors values: For BLUE and BLACK motor wires, the rightvalue is± 55ohms.
ForBLUEand BROWNmotorwires,therightvalue is ±35 ohms. ForBROWN
andBLACK motorwires,therightvalueis± 89ohms.Aluminum motorsvalues:
ForBLUEand BLACKmotorwires,therightvalueis±51 ohms.ForBLUEand
BROWN motor wires, the right value is ± 47 ohms. For BROWN and BLACK
motor wires, the right value is ± 98 ohms. If he ohms values are the same, the
motor is not defective. Replace the motor capacitor.
6. The defrost cycle
does not work (the
fresh air duct is fro-
zen OR the fresh air
distributed is very
cold. (See Table 7 for
Defrost Cycle Tim-
ing.)
S Ice deposits may be hindering the
damper operation.
S Remove the ice.
S The damper rod orthe port damperitself
may be broken.
S Inspect these parts and replace if necessary.
S The damper actuator or circuit board
may be defective.
S See Problem 2.
7. The integrated con-
trol push button does
not work.
S The 30--second boot sequence is not
completed.
S See Boot Sequence.
ERV / HRV