CFM HRV-48 Ventilation Hood User Manual


 
SSTTAANNDDAARRDD FFEEAATTUURREESS && BBEENNEEFFIITTSS
Supply or exhaust applications
Direct drive (HRVD) or belt drive (HRVB) arrangements
Spark resistant, cast aluminum airfoil axial impeller
Factory set adjustable pitch blades
Aerodynamically efficient performance
Heavy duty welded steel base
Air dried enamel paint finish
Aluminum hood with birdscreen
TEFC industrial duty motor
Direct drive units are easily maintained – no belts or pulleys
Belt drive units have self-aligning pillow block bearings
Belt drive units use v-belt drive for low speed operation
AAPPPPLLIICCAATTIIOONNSS
Fume and smoke exhaust General ventilation
Make-up air Filtered air supply
Heat exhaust
AACCCCEESSSSOORRIIEESS // OOPPTTIIOONNSS
Filtered intake unit 2” thick disposable filters, for filtered intake unit
Gravity shutter for exhaust only Variable pitch sheaves for easy & accurate adjustment
Pre-fabricated roof curb Disconnect switch – mounted, or mounted & wired
Custom curb panel to match existing curb Motor operated damper for supply or exhaust applications
Epoxy or Eisenheiss coatings Explosion proof & special duty motors
MODEL A B D E G
WT (LBS)
LESS MTR
MAX MTR
FRAME
HP
HRV-24 30 54 x 64 41.5 39 25.5 324 145T
1
/4 - 1
HRV-30 36 60 x 76 41.5 45 25.5 365 145T
1
/
3 - 1
1
/
2
HRV-36 42 72 x 82 45.5 51 27.5 410 145T
1
/3 - 2
HRV-42 48 80 x 89 45.5 57 27.5 503 184T
1
/
2 - 3
HRV-48 54 87 x 95 49.5 63 29.5 630 184T
3
/4- 5
HRV-54 60 92 x 98 50.5 69 29.5 870 215T 1 - 5
HRV-60 66 90 x 107 54.5 75 31.5 1140 215T 1 - 10
*DO NOT USE FOR CONSTRUCTION
CONSULT FACTORY FOR CERTIFIED PRINTS
DIMENSIONS IN INCHES*
HHRRVV HHOOOODDEEDD RROOOOFF VVEENNTTIILLAATTOORRSS
D
SQ. INSIDE BASE
E
B
A
FAN PANEL DIMENSION
G
DAMPER (OPTIONAL)
CURB
2-1/2”
MODEL
MINIMUM
CFM
MAXIMUM
CFM
MAXIMUM CFM
WITH FILTERS
HRV-24 800 6,700 4,861
HRV-30 800 11,800 11,800
HRV-36 1,800 15,376 13,889
HRV-42 3,300 22,296 16,000
HRV-48 4,283 30,900 18,750
HRV-54 8,000 35,238 19,333
HRV-60 9,600 47,000 21,333
PERFORMANCE RATING