Dometic TJF42 Refrigerator User Manual


 
3
12 VDC 12 VDC 24 VDC 24 VDC
cutout cutin cutout cutin
10.4 11.7 22.8 24.2
TJ18, TJ22, TJ42, TJF42 & TJ80 Installation And Operating Instructions
An overheating of the electronic unit heat sink will
cause the compressor to stop. Restart will occur
automatically when a normal temperature has been
reached.
4. Voltage Protection
If a voltage outside the operating range is applied
to the electronic unit, the compressor does not start,
or it stops if the voltage limit is exceeded during
operation. The compressor will restart automati-
cally approximately 1 minute after the supply volt-
age has reached the reset voltage within the range
in question.
5. Battery Protection
The electronic unit provides protection as follows:
Standard Battery Protection Settings
Length of Conductor from Source of Current to Device and Back to Source - Feet
10 15 20 25 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170
Total
Current
On Circuit
In Amps 12 Volts - 3% Drop Wire Size (gauge) - Based on Minimum CM Area
5 181614121210101088866666666
10 141210101086666444422222
15 1210108866644222221111
20 101086664422221110002/0
25 10866644222110002/02/02/03/0
30 108664422110002/02/03/03/03/03/0
40 86644221002/02/03/03/03/04/04/04/04/0
50 664422102/02/03/03/04/04/04/0
60 64422102/03/03/04/01 4/0 4/0
70 6422102/03/03/04/04/0
80 6422103/03/04/04/0
90 422102/03/04/04/0
100 422102/03/04/0
24 Volts - 3% Drop Wire sizes (gauge) - Based on Minimum CM Area
5 1818181616141212121010101010 8 8 8 8 8
10 181614121210101088866666666
15 1614121210108866666444442
20 141210101086666444422222
25 12121010866644442222221
30 1210108866444222221111
40 101086664422221110002/0
50 10866644222110002/02/02/03/0
60 108664422110002/02/03/03/03/03/0
70 866442211002/02/03/03/03/03/04/04/0
80 86644221002/02/03/03/03/04/04/04/04/0
90 8644221002/02/03/03/04/04/04/04/04/0
100 664422102/02/03/03/04/04/04/0
ABYC Standards - ABYC Guidelines E9 - Direct Current
Conductor Sizes For 3 % Drop in Voltage
See Amp Draw Chart Above To Determine Wire Size
Refrigerator Amperage
Model Amperage
12 VDC 24 VDC
TJ18, TJ22 & TJ42 3.72 1.86
TJF42 & TJ80 4.56 2.28