Electrolux 318201778 Range User Manual


 
4
36" GAS RANGE INSTALLATION INSTRUCTIONS
3. Gas Supply Installation
When shipped from the factory, this unit is designed to
operate on 4"(10,16 cm) water column (1.0 kPa) Natural
gas manifold pressure. A convertible pressure regulator is
connected to the range manifold and MUST be connected
in series with the gas supply line. The gas connector is
located as shown on figure 1. It is accessible from front of
the range.
For proper operation, the maximum inlet pressure to
the regulator should be no more than 14"(35,56 cm) of
water column pressure (3.5 kPa).
The inlet pressure to the regulator must be at least 1" (.25
kPa) greater than the regulator manifold pressure setting.
The regulator is set for 4"(10,16 cm) water column (1.0
kPa) Natural gas manifold pressure; the inlet pressure must
be at least 5"(12.60 cm) water column (1.25 kPa) Natural
gas. For LP/Propane gas, the regulator must be set for
10"(25,4 cm) water column (2.5 kPa) manifold pressure;
the inlet pressure must be at least 11"(27,9 cm) water
column (2.75 kPa).
The supply line should be equipped with an approved
shutoff valve (see Figure 3 & 4). This valve should be
located in the same room as the range and should be in a
location that allows ease of opening and closing. Do not
Suggested gas connections
All connections must be wrench-tightened
Figure 3
Manual
Shut-off
Valve
Flexible
Connector
90
o
Elbow
Connector
Assemble the flexible connector from the gas supply
pipe to the gas connector in the following order:
1. Manual shut-off valve (not supplied)
2. Flexible connector (not supplied)
3. 1/2" 90
o
Elbow Connector (not supplied)
4. Gas "T" connector (supplied)
Gas "T"
Connector
Connection to Pressure Regulator
The regulator is already installed on the appliance.
Do not make the connection too tight.
The regulator is die cast. Overtightening may crack the
regulator resulting in a gas leak and possible fire or
explosion.
The gas supply line to the shutoff valve should be
1/2"(1,27 cm) or 3/4"(1.9 cm) solid pipe.
The user must know the location of the main shutoff
valve and have easy access to it.
When using flexible gas conduit on the range, allow
sufficient slack to pull the range outside the cutout for
cleaning or servicing.
NOTE: Do not allow the flexible conduit to get pinched
between the wall and the range.
block access to the shutoff valve. The valve is for turning
on or shutting off gas to the appliance. Open the shutoff
valve in the gas supply line. Wait a few minutes for gas to
move through the gas line.
The gas supply between the shutoff valve and the
regulator may be connected by rigid piping or by A.G.A./
C.G.A.-approved flexible metallic union-connected piping
where local codes permit use.
The gas supply piping can be through the side wall of the
right cabinet. The right side cabinet is an ideal location for
the main shutoff valve, if the range is installed within
cabinet storage space
Shutoff Valve -
Open position
to appliance
to gas supply line
Figure 4
Use pipe-joint compound made for use with Natural and
LP/Propane gas to seal all gas connections. If flexible
connectors are used, be certain connectors are not kinked.
The supply line must be equipped with an approved
manual shutoff valve. This valve should be located in the
same room as the range and should be in a location that
allows ease of opening and closing. Do not block access
to the shutoff valve. The valve is for turning on or
shutting off gas to the appliance.
Once regulator is in place, open the shutoff valve in the
gas supply line. Wait a few minutes for gas to move
through the gas line.
Check for leaks. After connecting the range to the gas
supply, check the system for leaks with a manometer. If
a manometer is not available, turn on the gas supply and
use a liquid leak detector (or soap and water) at all
joints and connections to check for leaks. Leaks will be
indicated by bubbles appearing at the connections or
joints.