Frymaster FMCF Fryer User Manual


 
CF SERIES GAS FRYERS
CHAPTER 2: INSTALLATION INSTRUCTIONS
2-7
Gas Connection Pipe Sizes
[
Minimum incoming pipe size should be 1-1/2" (38 mm)]
Natural 3/4" (19 mm) 1" (25 mm)
1-1/4" (33 mm)
Propane 1/2" (13 mm) 3/4" (19 mm) 1" (25 mm)
Manufactured 1" (25 mm) 1-1/4" (33 mm) 1-1/2" (38 mm)
Gas Single Unit 2 - 3 Units
4 or more
units*
* For distances of more than 20 feet (6 m) and/or more than
four fittings or elbows, increase the connection by one pipe
size.
CE Standard
CE regulations require a combustion air supply of 2m
3
/h per kW per fryer. (See rating plate affixed
to door for kW rating.)
1. Connect the quick-disconnect hose to the fryer quick-disconnect fitting under the front of the
fryer and to the building gas line.
NOTE: Some fryers are configured for a rigid connection to the gas supply line. These units are
connected to the gas supply line at the rear of the unit.
When using thread compound, use very small amounts on male threads only. Use a pipe thread
compound that is not affected by the chemical action of LP gases (Loctite PST567 sealant is one
such compound). DO NOT apply compound to the first two threads. Applying compound to the
first two threads will cause clogging of the burner orifices and control valve.
2. Open the gas-supply valve to the fryer and check all piping, fittings, and gas connections for
leaks. A soap and water solution should be used for this purpose.
DANGER
All connections must be sealed with a joint compound suitable for the gas being
used and all connections must be tested with a solution of soapy water before
lighting any pilots.
Never use matches, candles, or any other ignition source to check for leaks. If gas
odors are detected, shut off the gas supply to the appliance at the main shut-off
valve and immediately contact the local gas company or an authorized service
agency for service.