H*
P
W*
H* P
102 20
127 20
152 23
178 28
203 30
229 33
254 33
279 36
305 41
330 43
356 46
381 46
406 51
432 53
457 56
483 58
508 61
533 66
559 66
584 69
610 74
635 79
660 81
686 81
711 84
737 86
762 91
787 94
813 94
838 99
864 99
889 104
914 107
SIZE LIMITATIONS
Vertical or Horizontal
Single Multi-
mm Section Section
Minimum 102 x 102 NA
Maximum 914 x 914 2438 x 1219
or 3048 x 1016
Installation of sizes larger than the maximums shown requires
approval of the authority having jurisdiction.
DFD-M150 Type A
SIZING AND ASSEMBLY DATA
Dampers larger than maximum single section size are supplied in 2 or more sections
of equal size. If ordered with a factory sleeve, multi-section dampers are factory
assembled ready for installation. If ordered without a factory sleeve, multi-section
dampers require field assembly. (See Greenheck Fire Damper Installation Instructions
#452763)
The following chart and illustrations show minimum and maximum damper section
size and assembly configurations for multi-section dampers.
1 2 3
Blade Stack
Dimensions
914mm max.
914mm max.
2438mm max.
1219mm max.
3048mm max.
1016mm max.
Mult-Section Limitations
Maximum damper height is 1016mm when combination width is
greater than 2438mm and less than or equal to 3048mm.
3
Multi-Section Limitations
Maximum damper height is 1219mm when combination width is 2438mm or less.
2
Maximum Single Section Dimensions
1
*
These dimensions are furnished
approximately 6mm undersize.
(Dimension in mm)