Greenheck Fan SP Ventilation Hood User Manual


 
19
DELUXE INLINE FAN
B
CSP
Performance certified is for Model CSP inline for installation type D: Ducted inlet, Ducted outlet. Performance ratings include the effects of a backdraft damper. Speed (RPM) shown
is nominal. Performance is based on actual speed of test. The sound ratings shown are loudness values in fan sones at 5 ft. (1.5m) from the test inlet duct in a hemispherical free field
calculated per AMCA Standard 301. Values are for installation type D: Ducted inlet fan sone levels. Ratings do not include the effects of duct end correction. Ratings are based on 10 ft.
of insulated duct. The AMCA Certified Ratings Seal applies to air performance only.
Dimensional Data
Performance Data
Model
A B C D E F G Wt.
110, 150, 200 13
7
/8 11
1
/2 7
15
/16 6 1
1
/4 10
1
/4 3
1
/4 10
1
/4
Model SP-C50
Ceiling mounted exhaust fans shall be of the centrifugal direct drive
type. The fan housing shall be constructed of steel. The plastic
duct collar shall be a tapered sleeve for ease of connection to
3 and 4 inch round ductwork and shall include a backdraft damper.
The grille shall be constructed of non-yellowing high impact
polystyrene and attached to the housing with torsion springs.
The wheels shall be constructed of high strength polymer. The
access for wiring shall be external. The motor disconnect shall
be internal and of the plug in type. All fans shall bear the AMCA
Certified Ratings Seal for sound and air performance. Model
SP-C50 shall be UL Listed. Fans shall be Model SP-C50 as supplied
by Greenheck Fan Corporation, Schofield, Wisconsin.
Models SP-B50, B70, B80, B90, B110, B150, and B200
Ceiling mounted exhaust fans shall be of the centrifugal direct
drive type. The fan housing shall be constructed of steel. The
steel duct collar shall be 4 inch in diameter on the B50, B70, and
B80 and 6 inch in diameter on the B90, B150, and B200 to accept
4 inch and 6 inch round ductwork and shall include a backdraft
damper. The designer grille shall be constructed of non-yellowing
high impact polystyrene and attached to the housing with hidden
attachment screws. The access for wiring shall be external. The
motor disconnect shall be internal and of the plug in type.
The motor shall be mounted on vibration isolators. The fan wheel
shall be of the forward curved centrifugal type, constructed of
calcium carbonate filled polypropylene and dynamically balanced.
All fans shall bear the AMCA Certified Ratings Seal for sound
and air performance and shall be UL/cUL Listed. Ceiling or wall
mount fans shall be Model SP-B50, B70, B80, B90, B110, B150 or
B200 as manufactured by Greenheck Fan Corporation, Schofield,
Wisconsin.
Models SP-A50 thru A1550
Ceiling mounted exhaust fans shall be of the centrifugal direct
drive type. The fan housing shall be constructed of heavy gauge
galvanized steel. The housing interior shall be lined with 1/2 inch
acoustical insulation. The outlet duct collar shall include an aluminum
backdraft damper on all SP-A sizes and shall be spring loaded on
size SP-A110 and larger. Outlet shall be adaptable for horizontal
or vertical discharge. The designer grille for sizes SP-A50 through
SP-A390 shall be constructed of high impact polystyrene and for
sizes SP-A410 through SP-A1550, the grille shall be constructed of
aluminum. Grilles shall be non-yellowing.
The access for wiring shall be external. The motor disconnect shall
be internal and of the plug in type. The motor shall be mounted on
vibration isolators. The fan wheel(s) shall be of the forward curved
centrifugal type and dynamically balanced. All fans shall bear the
AMCA Certified Ratings Seal for sound and air performance and
shall be UL/cUL Listed. Ceiling or wall mount fans shall be Model
SP as manufactured by Greenheck Fan Corporation, Schofield,
Wisconsin.
Models CSP-B110, B150, and B200
Duct mounted exhaust, supply or return air fans shall be of the
centrifugal direct drive type. The fan housing shall be constructed
of steel. The steel duct collar shall be 6 inch in diameter to accept
6 inch round ductwork and shall include a backdraft damper. The
access for wiring shall be external. The motor disconnect shall be
internal and of the plug in type.
The motor shall mounted on vibration isolators. The fan Wheel shall
be of the forward curved centrifugal type, constructed of calcium
carbonate filled polypropylene and dynamically balanced. All fans
shall bear the AMCA Certified Ratings Seal for air performance and
shall be UL/cUL Listed. Ceiling or wall mount fans shall be Model
CSP-B110, B150 or B200 as manufactured by Greenheck Fan
Corporation, Schofield, Wisconsin.
Models CSP-A110 thru A3600
Duct mounted exhaust, supply or return air fans shall be of the
centrifugal direct drive type. The fan housing shall be constructed
of heavy gauge galvanized steel. The housing interior shall be lined
with 1/2 inch acoustical insulation. The outlet duct collar shall
include an aluminum backdraft damper and shall be adaptable
for horizontal or vertical discharge. The access for wiring shall be
external. The motor disconnect shall be internal and of the plug in
type.
The motor shall be mounted on vibration isolators. The fan wheel(s)
shall be of the forward curved centrifugal type and dynamically
balanced. All fans shall bear the AMCA Certified Ratings Seal for
air performance and shall be UL/cUL Listed. Ceiling or wall mount
fans shall be Model CSP as manufactured by Greenheck Fan
Corporation, Schofield, Wisconsin.
CFM/Static Pressure in inches of WG
Model RPM AMPS
Watts
0.000 0.100 0.125 0.250 0.375 0.500 0.625 0.750
CFM 103 100 99 98 97 96 93 86
CSP-B110 950 1.14 80
Sones 2.0 2.0 2.1 2.3 2.6 2.7 3.1 3.3
CFM 151 149 149 148 147 145 142 134
CSP-B150 1050 1.70 129
Sones 2.5 2.7 2.7 2.9 3.1 3.4 3.6 3.9
CFM 186 184 183 182 180 178 175 169
CSP-B200 1100 2.20 173
Sones 3.4 3.6 3.7 4.0 4.1 4.1 4.3 4.5
4 Units available with 50 Hz motors (See CAPS for performance)
4,6
4,6
4,6
Outlet connection width is 1 inch - Mounting bracket width is 1½ inch
For complete dimensional information, see CAPS submittal drawings.
All dimensions are in inches.
C
A
B
D
d
i
a.
Inl
et
Fx
G
E
6 Available with 277 volt motor.
®
Typical SpecificationsTypical Specifications