Greenheck Fan WD-400 Series Ventilation Hood User Manual


 
1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 150
Static Pressure Difference (In. wg)
Air Leakage in cfm/ft
2
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
8.5
8.0
7.0
6.0
5.0
4.0
3.0
2.0
Velocity (fpm)
1
x 10
Pressure Loss ( in. wg)
2 3 4 5 6 7 8 9 10
x 100
2 3 4 5 6 7 8 9 10
x 1000
2 3 4 5 6 7 8 9 10
Start Open
Full Open
10.0
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.10
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
Velocity (fpm)
1
x 10
Pressure Loss (in. wg)
10.0
9.0
8.0
7.0
6.0
5.0
4.0
3.0
2.0
2 3 4 5 6 7 8 9 10
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.10
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
x 100
2 3 4 5 6 7 8 9 10
x 1000
2 3 4 5 6 7 8 9 10
Start Open
Full Open
Pressure Drop
36 in. x 36 in. (914mm x 914mm) Damper
Performance data results from testing a 36 in. x 36 in. (914mm x 914mm) damper in accordance with AMCA Standard 500-D
using Figure 5.3 for the WD-400 and Figure 5.7A for the WD-410. All data has been corrected to represent standard air at 0.075
lb/ft
3
(1.201 kg/m
3
).
Leakage
36 in. x 36 in. (914mm x 914mm) Damper
Leakage testing was conducted in accordance with AMCA
Standard 500-D and is expressed as cfm/ft
2
of damper face
area. All data has been corrected to represent standard air at
0.075 lb/ft
3
(1.201 kg/m
3
).
∆P Velocity
Operational Data
in. wg fpm
(Pa) (m/s)
Blades Start to Open 0.026 250
(6.5) (1.3)
Blades Fully Open 0.04 1200
(10) (6.1)
2
Pressure Drop
36 in. x 36 in. (914mmx 914mm) Damper
∆P Velocity
Operational Data
in. wg fpm
(Pa) (m/s)
Blades Start to Open 0.014 22
(3.5) (0.1)
Blades Fully Open 0.12 1000
(30 Pa) (5.1)
WD-400
WD-410
WD-400 SERIESPERFORMANCE DATA
Pressure Drop
Leakage