SPYDER® LON PROGRAMMABLE, VAV/UNITARY CONTROLLERS
62-0287—03 2
SPECIFICATIONS
General Specifications
Rated Voltage: 20–30 Vac; 50/60 Hz
Power Consumption:
100 VA for controller and all connected loads (including the
actuator on models PVL0000AS, PVL4022AS, and
PVL6436AS)
Controller Only Load: 20 VA maximum; models PUL1012S,
PUL4024S, PUL6438S, PVL4024NS, and PVL6438NS.
Controller and Actuator Load: 21 VA maximum; models
PVL0000AS, PVL4022AS, and PVL6436AS
External Sensors Power Output: 20 Vdc ±10% @ 75 mA
maximum
VAV Operating & Storage Temperature Ambient Rating
(models PVL0000AS, PVL4022AS, PVL4024NS,
PVL6436AS, and PVL6438NS):
Minimum 32 F (0 C); Maximum 122 F (50 C)
Unitary Operating & Storage Temperature Ambient Rating
(models PUL1012S, PUL4024S, and PUL6438S):
Minimum -40 F (-40 C); Maximum 150 F (65.5 C)
Relative Humidity: 5% to 95% non-condensing
LED: Provides status for normal operation, controller down-
load process, alarms, manual mode, and error conditions
BEFORE INSTALLATION
The controller is available in eight models (see Table 1).
Review the power, input, and output specifications on page 2
before installing the controller.
Hardware driven by Triac outputs must have a minimum
current draw, when energized, of 25 mA and a maximum
current draw of 500 mA.
Hardware driven by the analog current outputs must have
a maximum resistance of 550 Ohms, resulting in a
maximum voltage of 11 volts when driven at 20 mA.
If resistance exceeds 550 Ohms, voltages up to 18 Vdc are
possible at the analog output terminal.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring or
making wiring connections to prevent electrical shock
or equipment damage.
INSTALLATION
The controller must be mounted in a position that allows
clearance for wiring, servicing, removal, connection of the
LonWorks® Bus Jack, and access to the Neuron® Service
Pin.
The controller may be mounted in any orientation.
IMPORTANT
Avoid mounting in areas where acid fumes or other
deteriorating vapors can attack the metal parts of the
controller, or in areas where escaping gas or other
explosive vapors are present. See Fig. 4–Fig. 7 on
page 4 for mounting dimensions.
For PVL0000AS, PVL4022AS, and PVL6436AS models, the
actuator is mounted first and then the controller is mounted.
For the other models, go to “Mount Controller” on page 4 to
begin the installation.
Mount Actuator onto Damper Shaft
(PVL0000AS, PVL4022AS, and PVL6436AS)
PVL0000AS, PVL4022AS, and PVL6436AS controllers
include the direct-coupled actuator with Declutch mechanism,
which is shipped hard-wired to the controller.
The actuator mounts directly onto the VAV box damper shaft
and has up to 44 lb-in. (5 Nm) torque, 90-degree stroke, and
90 second timing at 60 Hz. The actuator is suitable for
mounting onto a 3/8 to 1/2 in. (10 to 13 mm) square or round
VAV box damper shaft. The minimum VAV box damper shaft
length is 1-9/16 in. (40 mm).
The two mechanical end-limit set screws control the amount
of rotation from 12° to 95°. These set screws must be securely
fastened in place. To ensure tight closing of the damper, the
shaft adapter has a total rotation stroke of 95° (see Fig. 1).
NOTE: The actuator is shipped with the mechanical end-limit
set screws set to 95 degrees of rotation. Adjust the
two set screws closer together to reduce the rotation
travel. Each “hash mark” indicator on the bracket
represents approximately 6.5° of rotation per side.
NOTE: The Declutch button, when pressed, allows you to
rotate the universal shaft adapter (see Fig. 1).
IMPORTANT
Determine the damper rotation and opening angle
prior to installation. See Fig. 2 and Fig. 3 on page 3
for examples.
Fig. 1. Series 60 Floating Actuator.
IMPORTANT
Mount actuator flush with damper housing or add a
spacer between the actuator mounting surface and
damper box housing.
UNIVERSAL SHAFT
CLAMPING BOLTS (2)
M23568
UNIVERSAL
SHAFT ADAPTER
MECHANICAL
END LIMIT SET
SCREWS (2)
DECLUTCH
BUTTON