Honeywell V4297S Ventilation Hood User Manual


 
V4297S NORMALLY OPEN VENT VALVE
65-0244
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Home and Building Control Sales Office (check white pages of your phone directory).
2. Home and Building Control Customer Logistics
Honeywell Inc., 1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
IMPORTANT
The specifications in this publication do not include
normal manufacturing tolerances; therefore, an
individual unit may not exactly match the
specifications listed. Also, this product is tested and
calibrated under closely controlled conditions, and
some minor differences in performance can be
expected if those conditions are changed.
Models:
V4297S Normally Open Vent Valve.
Type of Gas:
Natural, manufactured, mixed or liquefied petroleum (LP) only.
Gas Train Pipe Size:
3/4 in. (19 mm), 1 in. (25 mm), 1-1/4 in. (32 mm),
1-1/2 in. (38 mm), 2 in. (51 mm), 2-1/2 in. (64 mm),
3 in. (76 mm).
Pipe Threads:
Small Body: 1 in. NPT threaded vent connection.
Large Body: 1-1/4 in. NPT threaded vent connection.
Operating Pressure Rating:
Maximum: 5 psi.
Valve Capacity through Vent Connection:
Ratings: 1 in. (0.25 kPa) pressure drop for gas with 0.64 sp gr.
Small Body: 714 cfh.
Large Body: 1115 cfh.
Bolt/Nut Fasteners:
Bolts, nuts and O-rings are provided with the safety shutoff
valves.
Tapping and plug:
Taps:1/4 in. NPT taps.
Plugs: Allen head.
Ambient Operating Temperature Rating:
-40°F to +145°F (-40°C to +63°C).
Material:
Die-cast aluminum.
Mounting:
Bolted to Integrated Valve Train components.
Mounting Position:
Vertical to 90 degrees from vertical. See Fig. 1.
Fig. 1. Mounting positions for V4297S
Normally Open Vent Valve.
Electrical Terminations:
Screw terminal connections.
Current Draw:
V4297S small body, 120V: 0.2A.
V4297S large body, 120V: 0.34A.
Valve opening time: < 1 sec.
Valve closing time: < 1 sec.
Dimensions:
See Fig. 2 and 3.