Honeywell VNT5200H1000 Ventilation Hood User Manual


 
Specications(continued)
External Static
Pressure
Net Supply Air Flow
Gross Air Flow
Supply Exhaust
Pa in. W.C. L/s CFM L/s CFM L/s CFM
25 0.1 98 208 102 218 99 210
50 0.2 94 200 99 210 95 202
75 0.3 87 186 93 199 88 188
100 0.4 82 175 88 188 83 176
125 0.5 74 157 78 167 75 159
150 0.6 65 138 72 152 65 139
175 0.7 60 127 64 135 60 128
200 0.8 53 112 60 127 53 113
225 0.9 44 94 54 114 45 95
250 1 38 81 41 86 39 82
VNT5200E1000VentilationPerformance
VNT5200E1000EnergyPerformance
Supply Temperature Net Supply Air Flow
Average
Power
Sensible
Recovery
Apparent
Sensible
°C °F L/s CFM Watts Efficiency % Effectiveness %
Heating
0 32 35 74 75 58 69
0 32 50 106 100 51 66
0 32 70 149 126 44 64
-15 5 35 74 80 58 69
35 95 35 74 75
Total Recovery Efficiency = 53%
ERV/HRVVentilationSystems69-2480EF—01