Hoshizaki HR24A Refrigerator User Manual


 
27
7) Startup–EvapFM icon is on and Comp icon is ashing. EvapFM energizes.
2-min.Comp delay timer starts. Comp icon ashes until 2-min. Comp delay timer
terminates. Diagnosis: Check that CT LEDs and EvapFM icon turn on. Next, check
that EvapFM energizes. If not, conrm that DS is engaged. Check across DSfor 5VDC.
If 5VDC is not present, check DS activation lever and DScontinuity. Note:DScontacts
are open when DS is engaged. If 5VDC is present, check CBEvapFM connector for
12VDC. If 12VDC is not present, replace CB. If 12VDC is present, check EvapFM wiring
connector for loose connection, EvapFM continuity, and fan blade for binding.
8) Cool Down–EvapFM icon is on and Comp icon turns steady. EvapFM continues.
2-min. Comp delay timer terminates. Comp energizes and 3-min. Comp run timer
starts. Diagnosis: Conrm CTh is at least 4°Fabove setpoint. Next, check that Comp
energizes. If not, check CB Comp connector for 115VAC. If 115VAC is not present,
conrm CTh status. See "IV.C. Thermistor Check." If CTh is in range and 115VAC is not
present, replace CB. If 115VAC is present, and Comp is off, check Comp wire harness
connections. Next check Comp external protector (integrated with start relay), Comp
start components, and Comp motor winding continuity. If Comp energizes and the
cabinet does not cool down, check for air leaks around the door (gasket), a restriction in
the refrigeration circuit, or refrigerant leak.
9) Cool Down AchievedEvapFM icon is on. CTh cools to setpoint (default 39°F).
EvapFM continues. If Comp run time > 3-min., Comp icon turns off and Comp
de-energizes. If Comp run time<3-min., Comp continues until 3-min. Comp run timer
terminates, then Comp icon turns off and Comp de-energizes. Diagnosis: If CTh is
in range and Comp does not de-energize, conrm Comp run time > 3 min. If Comp
continues after 3-min. Comp run timer terminates, replace CB.
10) Cool Down RestartEvapFM icon is on. CTh warms to 4°F above setpoint (default
39°F). Compicon turns on and Comp energizes. 3-min. Comp run timer starts.
Diagnosis: See step 8above.
11) Defrost–EvapFM and Defrost icons are on. Cabinet Temperature is Displayed.
a) Automatic Defrost Initiation: 6-hr.DTterminates. 30-min. DT starts. EvapFM
continues. If Comp run time <3min., Comp icon and Comp continue until 3-min.
Comp run timer terminates. Once 3-min. Comp run timer terminates, Comp
icon turns off, Comp de-energizes, and defrost starts. Diagnosis: Has 6-hr. DT
terminated? If defrost icon is on, conrm that Comp de-energizes. If not, conrm
Comp run time >3min. If Comp continues after 3-min. Comp run timer terminates,
replace CB.
b) Manual Defrost Initiation: To initiate a manual defrost, press and hold the "+" button
until the defrost icon turns. 30-min.DTstarts. EvapFM continues. If Comp run time
<3 min., Comp icon and Comp continue until 3-min. Comp run timer terminates.
Once 3-min. Comp run timer terminates, Comp icon turns off, Comp de-energizes,
and defrost starts. Diagnosis: If defrost icon is on, conrm that Comp de-energizes.
If not, conrm Comp run time > 3min. If Comp continues after 3-min. Comp run timer
terminates, replace CB.