30
2. LED Lights and Audible Alarm Safeties
a) KM-1601SAH/3 "G" Control Board
At startup, a 5-second delay occurs while the control board conducts an internal timer
check. A beep occurs when the control switch is moved to the "ICE" position.
The red LED indicates proper control voltage and remains on unless a control voltage
problem occurs. The green LEDs 1 through 4 energize and sequence from initial startup
as listed in the table below. Note that the order of the LEDs from the outer edge of the
control board is 1, 4, 3, 2. For details, see "II.B. Sequence of Operation."
Sequence Step LED
Energized
Components
Time LEDs are On
Min. Max. Avg.
1-Minute Fill Cycle 4 WV 1 minute
Harvest Cycle 1, 4, 2 Comp, FM, WV,
HGV
2 minutes 20 minutes 3 to 5 minutes
Harvest Pump Timer 1, 3, 2 Comp, FM, PM,
HGV
0 seconds 50 seconds harvest pump timer
setting
Freeze Cycle 1 Comp, FM, PM, LLV 5 minutes freeze timer
setting
30 to 35 minutes
Pump-Out Cycle 1, 4*, 3, 2 Comp, FM, WV*,
PM, HGV
10 seconds 20 seconds *pump-out timer
setting
The built-in safeties shut down the unit and have alarms as listed below.
No. of Beeps
(every 3 sec.)
Type of Alarm Notes
1 High Evaporator Temp.
(temperature > 127°F (53°C))
Check for harvest problem (stuck HGV or relay), hot
water entering unit, or shorted thermistor.
2 Harvest Backup Timer
(harvest > 20 min. for two cycles
in a row)
Check for open thermistor, HGV not opening, TXV or
LLV leaking by, low charge, or inefficient Comp.
3 Freeze Timer
(freeze > freeze timer setting for
two cycles in a row)
Timer is factory set using S4 dip
switch 9 & 10
Check for F/S stuck closed (up), WV leaking by, HGV
leaking by, PM not pumping, TXV not feeding properly,
LLV not opening, low charge, or inefficient Comp.
To reset the above safeties, press the "ALARM RESET" button with the power supply on.
6 Low Voltage
(92Vac±5% or less)
Red LED turns off if voltage protection operates.
The control voltage safeties automatically reset when
voltage is corrected.
7 High Voltage
(147Vac±5% or more)
Legend: Comp–compressor; FM–fan motor; F/S–oat switch; HGV–hot gas valve;
LLV–liquid line valve; PM–pump motor; TXV–thermostatic expansion valve;
WV–inlet water valve