21
[d] CONTROLS AND ADJUSTMENTS
The Dip Switch is factory-adjusted to the following positions:
FOR MODELS WITH MECHANICAL BIN CONTROL:
Switch Nos. 1 and 2:
Used for adjustment of the Defrost Timer.
The Defrost Timer starts counting when the Thermistor reads a certain temperature
at the Evaporator outlet.
Switch Nos. 3 and 4:
Used for adjustment of the Drain Timer.
When a freeze cycle is completed, the Pump Motor stops, and the icemaker
resumes operation in 2 seconds. Then the Pump Motor drains the Water Tank
for the time determined by the Drain Timer. The Drain Timer also determines the
time to restrain completion of a defrost cycle, i.e. the minimum defrost time.
Switch Nos. 5 and 6:
Used for adjustment of the Drain Counter.
The Pump Motor drains the Water Tank at the frequency determined by the Drain
Counter.
Switch No. 7:
Used only on models with mechanical bin control. Dip Switch should be set “ON”.
(Models with bin thermostat, Switch No. 7 should be set in the “OFF” position.)
Switch No. 8:
Used only for checking the Controller Board. Usually set in OFF position.
FOR MODELS WITH THERMOSTAT :
DIP SWITCH NO. 1 2 3 4 5 6 7 8 9 10
KM-630MAH OFF OFF OFF OFF ON ON ON OFF ON OFF
KM-630MWH OFF OFF OFF OFF ON ON ON OFF OFF OFF
KM-630MRH OFF OFF OFF OFF ON ON ON OFF ON OFF
DIP SWITCH NO. 1 2 3 4 5 6 7 8 9 10
KM-630MAH OFF OFF OFF OFF ON ON OFF OFF ON OFF
KM-630MWH OFF OFF OFF OFF ON ON OFF OFF OFF OFF
KM-630MRH OFF OFF OFF OFF ON ON OFF OFF ON OFF