Hoshizaki MWH KML-631MAH Refrigerator User Manual


 
24
G. Installation of Remote Condenser Unit
WARNING
• Installation of remote condenser unit must be performed by properly trained and
EPA-certied service personnel.
• The remote condenser unit must be installed in accordance with applicable
national, state, and local codes and regulations.
• Failure to install the remote condenser unit within these guidelines may adversely
affect safety, performance, component life, and warranty coverage.
• Power supply and ground wire to the remote condenser unit are supplied from the
icemaker. For details, see section "II.G.6. Electrical Connection."
1. Location
NOTICE
• The remote condenser unit is intended for outdoor use. Normal operating ambient
temperature should be within -20°F to +122°F (-29°C to +50°C). Operation of the
remote condenser unit, for extended periods, outside of this normal temperature
range may affect icemaker performance.
• The maximum line length for the standard line sizes and refrigerant charge is
66feet (20 m). With larger line sizes and/or additional refrigerant, the maximum
line length is 100 feet (30.5 m). For details, see "II.G.4 Line Set Size and
Refrigerant Charge."
• The maximum vertical distance between the remote condenser unit and the
icemaker is 33 feet (10 m) above or 10 feet (3 m) below the icemaker. These
distances are measured tting to tting. See Fig. 9.
The remote condenser unit must be positioned in a permanent site under the following
guidelines:
• A rm and at site.
• A dry and well ventilated area with 24" (61cm) clearance at front and rear for proper air
circulation and ease of maintenance and/or service should they be required. See Fig. 10.
Fig. 9
Min. 24" (61 cm) Clearance
Air Air
Fig. 10
Icemaker
Remote
Condenser
Unit
Service Loop
Max.
33 Feet
(10 m)
Remote
Condenser
Unit
Max.
10 Feet
(3 m)
Icemaker
Service Loop