ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTION
REQUIREMENTS
This appliance must be installed and grounded on a
branch circuit by a qualified technician in accordance
with the National Electrical code ANSI/NFPA NO. 70 -
latest edition.
All wiring should conform to Local and NEC. This range
requires a single-phase, 3 wire, A.C 120/208V or 120/240V
60Hz electrical system. Use only a 3-conductor or a
4-conductor UL-listed range cord with closed-loop
terminals, open-end spade lugs with upturned ends
or similar termination. DO NOT install the power cord
without a strain relief.
A range cord rated at 40 amps with 120/240 minimum
volt range is required. If a 50 amp range cord is used, it
should be marked for use with 1
3
/
8
” diameter connection
openings. This appliance may be connected by means
of conduit or power cord. If conduit is being used, go to
page 10 for 3 wire conduit connections or page 11 for 4
wire conduit connections.
• New branch-circuit installations (1996 NEC)
for mobile homes, recreational vehicles, and
installations where local codes do not allow
grounding through the neutral wire require
a 4-conductor UL listed range cord or 4 wire
conduit connection.
• Power supply cord and plug should not be
modified. If it will not fit the outlet, have a
proper outlet Installed by a qualied electrician.
• Using an extension cord to connect the power is
prohibited. The way to connect the power cord
and plug directly is strongly recommended.
• Electrical ground is required on this appliance.
• You should make sure that the power cord is
not pinched by the range or heavy objects.
- Failure to do so can result in serious burns or
electrical shock.
WARNING
Specied power-supply-cord kit rating
Range rating, watts Specied
rating of power
supply-cord kit,
amperes
Diameter (inches) of Range
connection Opening
120/240 volts
3-wire
120/208 volts
3-wire
Power cord Conduit
8,750 - 16,500
16,501 - 22,500
7,801 - 12,500
12,501 - 18,500
40 or 50A
50
1
3
/
8
”
1
3
/
4
”
1
1
/
8
”
1
3
/
8
”
3, 4 - Wire electrical wall Receptacle
4 Wire receptacle (14-50R)
3 Wire receptacle (10-50R)
FIGURE 3
CONNECT RANGE CORD
The Rear Access cover must be removed. Loosen the two
screws with a screwdriver. The terminal block will then be
accessible.
For model : LRE Series
For model : LSE Series
For model : LDE Series
Terminal block
Drawer body
Access
cover
Power cord outlet
Cord/Conduit
connection
plate
Terminal block
Drawer body cover
(LSE series only)
Drawer body
Access cover
Cord/Conduit
connection plate
Power cord outlet
FIGURE 4
Terminal block
Rear of lower oven
Access
cover
Access cover
Cord/Conduit
connection
plate
Protection cover