Master Bilt MCR-33-102 Refrigerator User Manual


 
REFRIGERATION SYSTEM TECHNICAL SPECIFICATIONS
3
All condensing units must include a suction accumulator.
Pull down time reects time neces-
sary to lower listed quantity of food from 140°F to 40°F. All units listed contain R-404A refrigerant.
COND.
UNIT
MODEL* H.P.
BTUH
@ -10°F
SUCTION
TEMP.**
UNIT CONNECTION
SIZES
DIMENSIONS
SEE
DRAWING...
(PP. 4-5)
RECEIVER
PUMPDOWN
CAP. @ 90%
SHIP
WT.
(LB/KG)
MCA** MOP** RLA** LRA**
LIQUID
SUCTION
MCR-33-101, 200 LB. CAPACITY, 2 HOUR PULL DOWN TIME
MSLZ0101C 3 10,653 3/8 7/8 M2 11.4 200/91 20 30 11.1 77
MHLZ0121B 3 11,559 1/2 1-1/8 M2 11.4 260/118 30 45 19 105
MCLZ0111B 3 10,372 1/2 7/8 M2 11.4 330/150 24 35 14.7 86
MCLZ0111C 3 10,343 1/2 7/8 M2 11.4 330/150 19 25 10 82
MCR-33-101, 200 LB. CAPACITY, 1.5 HOUR PULL DOWN TIME
MSLZ0151C 4 14,994 1/2 7/8 M2 11.4 230/105 32 40 15 99
BSLZ0400B 4 15,047 1/2 7/8 C 41.5 510/232 42 60 26.8 129
BSLZ0400C 4 15,047 1/2 7/8 C 41.5 510/232 32 40 15 99
BSLZ0400E 4 15,047 1/2 7/8 C 41.5 510/232 20 20 8.2 50
BCLZ0280B 3 15,529 5/8 1
1
/
8
C 41.5 505/230 32 40 15 105
BCLZ0280C 3 15,529 5/8 1
1
/
8
C 41.5 505/230 32 35 12.6 112
BCLZ0280E 3 15,529 5/8 1
1
/
8
C 41.5 505/230 20 20 6.2 56
MCR-33-101, 250 LB. CAPACITY, 2 HOUR PULL DOWN TIME
MSLZ0151C 4 14,994 1/2 7/8 M2 11.4 230/105 32 40 15 99
MCLZ0141B 3 13,799 1/2 1
3
/
8
M2 11.4 500/227 28 40 16.7 105
MCLZ0141C 3 13,903 1/2 1
1
/
8
M2 11.4 500/227 26 35 12.8 112
BSLZ0400B 4 15,047 1/2 7/8 C 41.5 510/232 42 60 26.8 129
BSLZ0400C 4 15,047 1/2 7/8 C 41.5 510/232 32 40 15 99
BSLZ0400E 4 15,047 1/2 7/8 C 41.5 510/232 20 20 8.2 49.5
BCLZ0280B 3 15,529 5/8 1
1
/
8
C 41.5 505/230 32 40 15 105
BCLZ0280C 3 15,529 5/8 1
1
/
8
C 41.5 505/230 32 35 12.6 112
BCLZ0280E 3 15,529 5/8 1
1
/
8
C 41.5 505/230 20 20 6.2 56
MCR-33-101, 250 LB. CAPACITY, 1.5 HOUR PULL DOWN TIME
MSLZ0181C 5 18,945 1/2 1
1
/
8
M3 15.2 240/109 36 55 21.4 123
MDLZ0201C 3 19,518 1/2 1
1
/
8
M3 15.2 530/241 38 45 16.8 102
MCR-33-101, 250 LB. CAPACITY, 1.3 HOUR PULL DOWN TIME
BSLZ0600C 6 21,651 1/2 7/8 C 41.5 550/250 41 60 23.9 156
BCLZ0400C 4 21,531 5/8 1
3
/
8
C 41.5 530/230 44 60 26.3 161
BCLZ0400E 4 21,531 5/8 1
3
/
8
C 41.5 530/230 22 30 10.2 60
BSLZ0600E 6 21,651 1/2 7/8 C 41.5 550/250 21 25 9.3 70
MCR-33-101 250 LB. CAPACITY, LESS THAN 1 HOUR PULL DOWN TIME
BCLZ0750C 7
1
/
2
37,322 7/8 1
3
/
8
D 53.4 730/332 55 80 31.5 161
BCLZ075UE 7
1
/
2
37,322 7/8 1
3
/
8
D 53.4 730/332 32 40 16.1 83
MCR-33-101 250 LB. CAPACITY, LESS THAN 1 HOUR PULL DOWN TIME – WATER COOLED CONDENSING UNITS
SCLZ075WC 7
1
/
2
39,600 5/8 1
3
/
8
D 78.4 730/332 50 80 31.5 161
SCLZ075WE 7
1
/
2
39,600 5/8 1
3
/
8
D 78.4 750/341 32 40 16.1 83
MCR-33-102, 400 LB. CAPACITY, 2 HOUR PULL DOWN TIME
MSLZ0221C 6 23,018 1/2 1
1
/
8
M5 17 250/114 39 60 23.9 156
MDLZ0231C 4 22,958 1/2 1
1
/
8
M3 15.2 530/241 42 60 26.3 161
BCLZ040LC 4 23,171 5/8 1
3
/
8
C 41.5 530/241 45 70 26.3 161
MCR-33-102, 400 LB. CAPACITY, 1.5 HOUR PULL DOWN TIME
MDLZ0291C 6 29,187 5/8 1
3
/
8
M5 17 560/255 47 70 28.2 161
MCR-33-102, 500 LB. CAPACITY, 2 HOUR PULL DOWN TIME
MDLZ0291C 6 29,187 5/8 1
3
/
8
M5 17 560/255 47 70 28.2 161
BSLZ0750C 7
1
/
2
26,006 1/2 7/8 C 41.5 550/250 54 80 30.9 189
BCLZ0600C 6 26,466 5/8 1
3
/
8
C 41.5 560/255 46 70 28.2 161
BCLZ0600E 2 26,466 5/8 1
3
/
8
C 41.5 560/255 26 35 13.3 80
*VOLTAGE KEY:
“B” sufx = 208-230 or 230 volt, 60 cycle, one phase
“C” sufx = 200-230 or 208-230 volt, 60 cycle, three phase
“E" sufx = 460 volt, 60 cycle, three phase
**Based on 90°F ambient
***Electrical ratings for condensing unit only. See National
Electrical Code if units are combined on a single circuit.