Miele DA 210-2 Cooktop User Manual


 
Ceiling plate: DA 200-2, DA 200-2 EXT
Ceiling plate: DA 210-2 / 210-2 EXT
Ceiling plate: DA 220-2 / 220-2 EXT
^
Address the ceiling plate and posi
-
tion it exactly. The orange coloured
arrow on the ceiling plate must face
to the front of the cooker hood.
Mark the position of the four holes to
be drilled a for securing the ceiling
plate and the position of the hole for
feeding the mains cable b through.
Select the cut-out providing the short
-
est route for the mains connection
cable b to reach the cooker hood
connector.
^
If the cooker hood is to be connected
to an external fan motor, also mark
the position of gap c for the connec-
tion cable.
^ Lay the mains cable and the exhaust
ducting C 150 mm in the ceiling
space.
If site conditions are not suitable for
C 150 mm ventilation ducting then
C 125 mm ventilation ducting can be
used, in which case a suitable reducing
collar is needed which can be pur
-
chased from your supplier or from the
Spare Parts Dept., (see "Installation –
Extraction" for further details).
Installation
26