Monessen Hearth WR400 Cooktop User Manual


 
14
WR / WC Series Woodburning Fireplace
20014528


Follow the installation instructions provided with the
chimney termination you have selected.

Refer to Page 5, Figure 5 for an illustration of a typical
chase installation.
 Treatment of firestop spacers and construc-
tion of chase may vary with type of building. These
instructions are not a substitute for local building codes.
You  check your local building codes to determine
specific requirements for your city or state. 
Other building materials may be required in addition to
Firestop Spacers.

All joints between the finished wall and
the fireplace surround (top/sides) must be sealed with
noncombustible material to prevent cold air leakage into
the room. Only noncombustible material may be applied
to the facing of the fireplace surround. (Black painted
area) (Fig. 20)

Finish the wall with material of your choice. 







 If a combustible material is used below a flat man-
tel shelf, consult your local building codes for minimum
clearance from top of fireplace opening to bottom of
mantel shelf.
All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must
be completely sealed with a noncombustible material.
(Figs. 21 and 22)
 No side wall protection is required for fireplaces
installed at 45° to two (2) side walls (corner installation).
Often a decorative surround or vertical portion of the
mantel is desired. If this is constructed of any combus-
tible material it must be within the safe zone indicated in
Figure 23.
FP559
Minimum clearances to combustibles.
Front View
Side View
Standoff
Combustible framing material MUST NOT
penetrate AIR SPACE (shaded areas).
Air Space Clearances
Only noncombustible
material may be applied
as facing to the black
fireplace surround.
Wall
Shield
Hearth
Extension
0" Clearance
to Floor
Firestop
1/2" Air
Space
to Back
1/2" Air
Space
to Sides
FP559
BR/BC-AIR SPACES
11/10/97
156O"
1/2" air space
to sides