Lifebreath 120ERV Ventilation Hood User Manual


 
2
3
2
1
20
40
60
80
100
120
140
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9
Static Pressure (in w.g.)
Air Flow (cfm)
3 - High Speed
2 - Medium Low Speed
1 - Low speed
Engineering Data
Model RNC120F
THERMALLY CONDUCTIVE, PATENTED ALUMINUM CORE
The cross-flow heat recovery core transfers heat between the two airstreams. It is easily
removed for cleaning or service.
MOTORS AND BLOWERS
Each Air stream has an independent motorized impeller. 3 speed operation 120VAC
FILTERS
Washable air filters in exhaust and supply air streams.
MOUNTING THE HRV
Four threaded inserts at corners of case designed to accept four reinforced polyester
straps that are supplied with the unit.
DEFROST
Fan defrost system. Fresh air motor turns off and Exhaust motor switches to high speed
to defrost core.
CASE
Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance.
Insulated to prevent exterior condensation. Drain connection 1 -
1
/2" (12 mm) OD.
CONTROLS
Unit is supplied with a remote HRV control box which can be conveniently located within
3’-0” of the HRV.
HRV System Control
HRV defaults to LOW SPEED when plugged in. HIGH SPEED option is accessible by
connecting remote controls to designated terminals inside electrical box of HRV.
Standard LOW SPEED SETTING can be increased to medium low.
Off (Standby)/Low or OFF/HIGH speed operation is also available.
DUCT CONNECTIONS
5” duct connections with “field” selectable standard airflow or reverse airflow for limited
room installations.
WEIGHT 42 lbs. (19 kg)
SHIPPING WEIGHT 45 lbs. (20.5 kg)
OPTIONAL ACCESSORIES
99-132 20 Minute Fan Timer - initiates high speed ventilation for 20 minutes. (3 wire)
20 gauge wire (min.) 100’ length
99-101 Crank Timer
99-116 Dehumidistat Ventilation Control - Dehumidistat with ON/OFF
99-130 Dehumidistat Control - Dehumidistat
99-185 Weatherhoods, Two - 5” (125mm) c/w
1
/4” (6mm) mesh screen
99-2040 20/40 ON/OFF Dehumidistat
WARRANTY
Units carry a lifetime warranty on the heat recovery core and a five year replacement
parts warranty.
FRESH AIR
FROM
OUTSIDE
EXHAUST
AIR FROM
BUILDING
FRESH AIR
TO BUILDING
EXHAUST AIR
TO OUTSIDE
TOP VIEW
SERVICE CLEARANCE FROM
BOTTOM OF UNIT IS MINIMUM 3'0"
9”
19”
18”
All Duct Collars are
5" diameter (127 mm)
Date: ______________________________________________
Tag: ________________________ Qty: __________________
Project:_____________________________________________
Engineer: ___________________________________________
Contractor: __________________________________________
Supplier:____________________________________________
Quote#: ____________________________________________
Submitted by:________________________________________
*Sensible Efficiency - thermal **Latent Efficiency - moisture
Note: Effectiveness - based on temp. differential between the 2 airstreams
Efficiency - takes into account all power inputs
Performance
Net supply air flow in cfm (L/s) against external static pressure
E.S.P
(external static pressure) [cfm (L/s)]
@ 0.1" (25 Pa) 125 (59)
@ 0.2" (50 Pa) 120 (56)
@ 0.3" (75 Pa) 114 (54)
@ 0.4" (100 Pa) 109 (51)
@ 0.5" (125 Pa) 106 (50)
@ 0.6" (150 Pa) 99 (47)
@ 0.7" (175 Pa) 94 (44)
@ 0.8" (200 Pa) 89 (42)
Sensible Effectiveness
@ 65 cfm (30 L/s) 32°F (0°C) 72%
*Sensible Efficiency
@ 65 cfm (30 L/s) 32°F (0°C) 55%
*Sensible Efficiency
@ 65 cfm (30 L/s) -13°F (-25°C) 45%
VAC @ 60HZ 120
WATTS / Low speed. 63
WATTS / High speed 150
Amp rating 1.5
All units conform to CSA
and UL standards.