Powerex MPD0508 Food Saver User Manual


 
Medical Package System
4
Specifications
Medical Package Duplex – Model MPD
Medical Package Triplex – Model MPT
Medical Package Quadplex – Model MPQ
MODEL HP PHASE RPM VOLTAGE
MPD0508 5(2) 3 33.4 36.2 870 208/230/460 17.4 /16.5 /8.2 120 64 x 65 x 76 1288
MPD0758 7.5(2) 3 52.2 55.1 840 208/230/460 23.4 / 22 /11 120 64 x 65 x 76 1340
MPD1008 10(2) 3 70 76.3 1070 208/230/460 29 /33 /16.5 200 64 x 65 x 80 1510
MPD1508 15(2) 3 108.4 114.1 1250 208/230/460 51/ 48 /24 200 64 x 65 x 80 1630
FULL LOAD AMP/
MOTOR
SCFM
@
100 PSIG
SCFM
@
50 PSIG
GALLON
TANK
DIMENSION
LxWxH
SHIPPING
WT. (Lbs.)
MODEL HP PHASE RPM VOLTAGE
MPT0508 5(3) 3 50.1 54.7 870 208/230/460 17.4 / 16.5/ 8.2 200 96 x 65 x 80 1838
MPT0758 7.5(3) 3 78.8 83.9 840 208/230/460 23.4 / 22 / 11 200 96 x 65 x 80 1980
MPT1008 10(3) 3 105 111.5 1070 208/230/460 29 / 33 / 16.5 240 96 x 65 x 92 2160
MPT1508 15(3) 3 162.6 168 1250 208/230/460 51/ 48 /24 240 96 x 65 x 92 2280
FULL LOAD AMP/
MOTOR
SCFM
@
100 PSIG
SCFM
@
50 PSIG
GALLON
TANK
DIMENSION
LxWxH
SHIPPING
WT. (Lbs.)
MODEL HP PHASE RPM VOLTAGE
MPQ0508 5(4) 3 66.8 74.9 870 208/230/460 17.4/ 16.5/ 8.2 240 128 x 65 x 92 2388
MPQ0758 7.5(4) 3 104.4 120.2 840 208/230/460 23.4 / 22/ 11 240 128 x 65 x 92 2490
MPQ1008 10(4) 3 140 153 1070 208/230/460 29 / 33 / 16.5 240 128 x 65 x 92 2640
MPQ1508 15(4) 3 216.8 221 1250 208/230/460 51 / 48 / 24 240 128 x 65 x 92 2735
FULL LOAD AMP/
MOTOR
SCFM
@
100 PSIG
SCFM
@
50 PSIG
GALLON
TANK
DIMENSION
LxWxH
SHIPPING
WT. (Lbs.)
Medical
Air Schematic
BEFORE START UP
1. Make sure all safety warnings, labels
and instructions have been read and
understood before continuing.
2. Remove any shipping materials,
brackets, etc.
3. Confirm that the electric power
source and ground have been firmly
connected.
4. Be sure all pressure connections are
tight.
5. Check to be certain all safety relief
valves, etc., are correctly installed.
6. Check that all fuses, circuit breakers,
etc., are the proper size.
7. Make sure the inlet filter is properly
installed.
8. Confirm that the drain valve is closed.
9. Visually check the rotation of the
compressor pump. If the rotation is
incorrect, have a qualified electrician
correct the motor wiring.
START-UP AND OPERATION
1. Follow all the procedures under
Before start-up before attempting
operation of the compressor.
2. Switch the electric source breaker
on.
3. Both dryers should be plugged in
and set at the on position.
4. Dewpoint & CO Monitors should be
on and the sampling valves open.
Calibrate Dewpoint and CO per
enclosed manufacturers
instructions.
5. Ensure water lines are properly
installed to water-cooled
aftercoolers. Turn on water.
IMPORTANT: This is not a standard
option. Check to see if water-
cooled aftercoolers were provided.
6. Compressor unit isolation valves are
preset at the factory in the open
position except for tank by-pass
which must remain closed during
normal operation.
7. Dryer and filter isolation valves:
Valves should be open to one dryer
and one filter bank.
8. Close valve leading to the Medical
Air System from receiver on the
compressor unit.
a. Turn both fusible/breaker
disconnects to the on position.
Low pressure alarm will sound.
Silence the alarm by pushing alarm
acknowledge button.
b. Jog each compressor in the manual
position on the selector switch to
check for rotation. (Clockwise if