Raypak 181/182 Ventilation Hood User Manual


 
Warnings 3
Pay Attention to These Terms 3
Receiving Equipment 4
General Specifications 4
Installation 4
Mounting the Assembly 4
Wiring a Power Vent Assembly to
an Appliance with IID Ignition 7
Venting 7
Wiring Diagrams 9
182-260 H4/WH1 (Atmospheric) 9
181-261 H4/WH1 (Low NOx) 10
330-400 H4/WH1 (Atmospheric) 11
331-401 H4/WH1 (Low NOx) 12
Sequence of Operation 14
Start Up Procedures 14
Draft Proving Switch 14
Illustrated Parts List 15
CONTENTS
3
DANGER:
Indicates the presence of immediate hazards which will cause severe
personal injury, death or substantial property damage if ignored.
WARNING:
Indicates the presence of hazards or unsafe practices which could cause
severe personal injury, death or substantial property damage if ignored.
CAUTION:
Indicates the presence of hazards or unsafe practices which could cause
minor personal injury or product or property damage if ignored.
NOTE:
Indicates special instructions on installation, operation, or maintenance which
are important but not related to personal injury hazards.
WARNINGS
Pay Attention to These Terms
NOTE: Minimum 18 AWG, 105°C, stranded wire
must be used for all low voltage (less than 30 volts)
external connections to the unit. Solid conductors
should not be used because they can cause
excessive tension on contact points. Install conduit
as appropriate. All high voltage wires must be the
same size (105°C, stranded wire) as the ones on the
unit or larger.