Smeg A1-2SE Range User Manual


 
Instructions for the installer
The manufacturer declines all responsibility for damage to persons
or things caused by non-observance of the above prescriptions or by
interference with any part of the appliance.
2.2 Ventilation requirements
The room containing the appliance should have an air supply in
accordance with B.S. 5440 part 2 1989.
1. All rooms require an opening window or equivalent, and some
rooms will require a permanent vent as well.
2. For room volumes up to 5 m
3
an air vent of 100 cm
2
is required.
3. If the room has a door that opens directly to the outside, and the
room exceeds 1 m
3
no air vent is required.
4. For room volumes between 5 m
3
and 10 m
3
an air vent of 50 cm
2
is
required.
5. If there are other fuel burning appliances in the same room B.S.
5440 part 2 1989 should be consulted to determine the air vent
requirements.
6. This appliance must not be installed in a bed sitting room of less
than 20 m
3
or in a bathroom or shower room.
Windows and permanent vents should therefore not be blocked or
removed without first consulting a Corgi gas installer.
Failure to install appliances correctly is dangerous and could lead
to prosecution.
2.3 Connecting to natural and LPG gas (Please see
connection diagram)
This type of connection is possible on both built-in and
free-standing appliances. Make the connection to the
appliance using flexible bayonet style hose in
accordance to B.S. 669. The hose connection at the
rear of the appliance has a ½” BSP internal thread.
Please use seal C between the flexible connection L
and the appliance supply tube B.
After completing the installation, check for any
leaks with a soapy solution, never with a naked
flame. Make sure that the hose complies with the
regulations in force.
When connecting to an LPG cylinder use a pipe with
adapter for connection to the pressure regulator.
If connecting to LPG the bayonet hose must have
red bands on it.
Take care that the hose is not crushed or damaged.
39