Instructions for the installer
12
5.2 Regulation for LPG
Loosen screw A and push support B all the way. Use a double head
wrench to remove nozzle C and assemble the suitable one, following the
instructions indicated in the reference charts, with respect to the type of
gas to use. The screwing torque of the nozzle should never exceed
3 Nm. Reposition support B so that nozzle C is covered perfectly.
Move the Venturi tube D to regulate the air flow until distance "X" is
reached indicated in the chart in paragraph "
5.4 Regulation of primary air
and then secure the tube by means of screw A. After the regulations
have been carried out, restore the seals with sealing wax or equivalent
material.
Burner
Rated
heating
capacity
(kW)
LPG – G30/G31 28/37 mbar
Nozzle
diameter
1/100 mm
By-pass
mm
1/100
Reduced
flowrate
(W)
Flowrate
g/h G30
Flowrate
g/h G31
Auxiliary (1) 1.05 48 30 380 76 75
Semi-rapid (2) 1.65 62 30 380 120 118
Rapid (3) 3.1 85 43 750 225 222
internal (5) 1.15 42 26 380 84 82 Double crown
external (5) 3.8 95 55 1200 276 271