Smeg PTSA727X Cooktop User Manual


 
Instructions for the Installer
3.1 Clearance above and around domestic appliances
Extract from AS5601
REQUIREMENTS
1 Overhead clearances – (Measurement A)
Range hoods and exhaust fans shall be installed in accordance with the
manufacturer’s instructions. However, in no case shall the clearance between the
highest part of the hob of the cooking appliance and a range hood be less than 600
mm or, for an overhead exhaust fan, 750 mm.
Any other downward facing combustible surface less than 600 mm above the
highest part of the hob shall be protected for the full width and depth of the cooking
surface area in accordance with Clause 5.12.1.2. However, in no case shall this
clearance to any surface be less than 450 mm.
2 Side clearances – (Measurements B & C)
Where B, measured from the periphery of the nearest burner to any vertical combustible
surface, is less than 200 mm, the surface shall be protected in accordance with
Clause 5.12.1.2 to a height C of not less than 150 mm above the hob for the full
dimension (width or depth) of the cooking surface area. Where the cooking
appliance is fitted with a ‘splashback’, protection of the rear wall is not required.
3 Additional requirements for Freestanding and Elevated Cooking Appliaces –
(Measurements D & E)
Where D, the distance from the periphery of the nearest burner to a horizontal
combustible surface is less than 200 mm, then E shall be 10 mm or more, or the
horizontal surface shall be above the trivet. See insets above.
8