GP Series Portable Chillers Chapter 3: Installation 22 of 64
Figure 6: Ethylene Glycol and Propylene Glycol Curves
Pe
r
ce nt Gly
c
ol Curves
f
or Free ze P
r
ote
c
tion
-60.0
-50.0
-40.0
-30.0
-20.0
-10.0
0.0
10.0
20.0
30.0
40.0
0.0 10.0 20.0 30.0 40.0 50.0 60.0
% Gl ycol by Volum e
Eth ylene G lycol
Propylene Glycol
Example: 45°F set point minus 20°F = 25°F.
From Figure 28, 25°F equates to 10% by volume of glycol required.
Note: The standard pumps used in the GPAC Serice chillers are not recommended to
be used with fluid below 0°F (-18°C). Please consult factory for the proper
pump.