13
Electrical Installation
All model ovens on the front cover are dual rated, designed to be connected to ei-
ther 208/240V AC, 60 Hz, 4 wire, single-phase power supply.
The electrical supply should be a 4-wire single-phase AC. Install a suitable conduit
box (not furnished).
Important: Local Codes may vary, installation, electrical connections and ground-
ing must comply with all applicable local codes.
If local codes permit grounding through the electrical supply neutral, connect both
the white neutral wire and the bare ground wire from the oven to the white neutral
electrical supply wire.
Electrical Connection
1. Connect the red oven wire to the red electrical supply wire (hot wire).
2. Connect the black oven wire to the black electrical supply wire (hot wire).
3. Connect the white neutral oven wire to the white neutral (not bare ground)
electrical supply wire.
4. Connect the bare ground oven wire to the bare ground electrical supply wire.
The conduit cable, where connected at the oven, swivels. Rotate conduit cable up-
ward (or downward) and direct through hole prepared in cabinet to attach to J-Box.
To facilitate maintain serviceability, the flex conduit must not be shortened and
should be routed to permit temporary removal of the oven.
Model Circuit Required
208V, 60 Hz 240V, 60 Hz
M271, M301 25 AMP 30 AMP
ME301, MEW301
ME271, PO301,
POD301, DE301,
DEC301
30 AMP 30 AMP
ME302, MED302
ME272, MED272,
PO302, POD302,
PODC302, DE302,
MEM271, MEM301,
POM301, MEMC301,
MEMCW301,
MEMW271, MEMW301,
POMW301
40 or 50 Amp circuit. Refer to local electrical codes
for de-rating requirements.