INSTALLATION / OPERATION INSTRUCTIONS
INSTALLATION / OPERATION INSTRUCTIONS
115
Volt
Amps
20 30 40 50 60 70 80 90 100 120 140 160
Distance in Feet to Center of Load.
Wire Gauge for 2% Voltage Drop in Supply Circuits
2
3
4
5
6
7
8
9
10
12
14
16
18
20
25
30
35
40
45
50
14
14
14
14
14
14
14
14
14
14
14
14
14
14
12
12
10
10
10
10
14
14
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
14
14
14
14
14
14
14
12
12
12
10
10
10
10
8
8
6
6
6
6
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
6
6
5
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
6
5
5
4
14
14
14
14
12
12
12
10
10
10
8
8
8
8
6
6
5
5
4
4
14
14
14
12
12
12
10
10
10
8
8
8
8
6
6
6
5
4
4
3
14
14
14
12
12
10
10
10
10
8
8
8
8
6
6
5
4
4
3
3
14
14
12
12
10
10
10
8
8
8
6
6
8
6
5
4
4
3
3
2
14
14
12
10
10
10
8
8
8
8
6
6
8
5
4
4
3
2
2
1
14
12
12
10
10
8
8
8
8
6
6
6
5
5
4
3
2
2
1
1
230Volt
Amps
20 30 40 50 60 70 80 90 100 120 140 160
Distance in Feet to Center of Load.
Wire Gauge for 2% Voltage Drop in Supply Circuits
5
6
7
8
9
10
12
14
16
18
20
25
30
35
40
50
60
70
80
90
100
14
14
14
14
14
14
14
14
14
14
14
14
14
14
14
12
12
10
10
10
10
14
14
14
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
14
14
14
14
14
14
14
14
14
14
14
12
12
10
10
10
8
8
8
6
6
14
14
14
14
14
14
14
14
14
12
12
12
10
10
10
8
6
6
6
6
6
14
14
14
14
14
14
14
14
12
12
10
10
10
10
8
6
6
6
6
5
5
14
14
14
14
14
14
14
12
12
12
10
10
10
8
8
6
6
6
5
5
4
14
14
14
14
14
14
12
12
12
10
10
10
8
8
8
6
6
5
5
4
4
14
14
14
14
14
12
12
12
10
10
10
10
8
8
6
6
6
5
4
4
3
14
14
14
14
12
12
12
10
10
10
10
8
8
8
6
6
5
5
4
3
3
14
14
14
12
12
13
10
10
10
8
8
8
6
6
6
5
4
4
3
3
2
14
14
12
12
12
10
10
10
8
8
8
6
6
6
5
4
4
2
2
1
1
14
12
12
12
10
10
10
8
8
8
8
6
6
5
5
4
3
2
2
1
1