PLANNING AND DESIGN GUIDE
VIKINGRANGE.COM 1-888-VIKING1
RELEASED 05/12/08
©2007 VRC—INFORMATION SUBJECT TO CHANGE
VENTILATION
Built-In Custom Ventilator Systems
Proper installation/ ducting is
extremely important to ensure
maximum performance. Use a qualified
and trained installer.
DUCTING
Check with a qualified and
trained installer or local codes
for makeup air requirements, if
any.
Max. duct run length
o For 300 – 1,200 CFM—
50’ (152.4 m)
o
For 1,500 CFM—75’ (22.9 m)
o Duct run length is for
general reference only;
always use a qualified and
trained installer.
o Straight runs and gradual
turns are best; for example,
each 90° elbow is equivalent
to 5’ – 10’ (1.52 3.05 cm)
of straight run.
7” (17.8 cm) round duct for
300 600 CFM; 10” for 900 –
1500 CFM
o Never use flexible duct; it
creates back pressure/air
turbulence and greatly
reduces performance.
GAS
Not applicable
ELECTRICAL
Hardwire direct with two-wire
ground
120 VAC/60 Hz
Max. amp usage (rating
includes recommended
ventilator kit rating)—see
Installation Requirements
table
PLUMBING
Not applicable
Installation Requirements
Model Ventilator Kits Duct Size Max. Amps
Interior Exterior Interior Exterior Interior Exterior
VBCV3038 VIV300/600/1200* VEV900/1200* 7” (17.8 cm)/ 10” (25.4 cm) 5.0/6.2/8.7 8.7/6.1
10” (25.4 cm)
VBCV3638 VIV300/600/1200* VEV900/1200* 7” (17.8 cm)/ 10” (25.4 cm) 5.0/6.2/8.7 8.7/6.1
10” (25.4 cm)
VBCV4238 VIV600/1200* VEV900/1200* 7” (17.8 cm)/ 10” (25.4 cm) 6.2/8.7 8.7/6.1
10” (25.4 cm)
VBCV4838 VIV1200* VEV1200*/1500 10” (25.4 cm) 10” (25.4 cm) 11.1 8.4/9.1
VBCV5438 VIV1200* VEV1200*/1500 10” (25.4 cm) 10” (25.4 cm) 11.1 8.4/9.1
VBCV6038 VIV1200* VEV1200*/1500 10” (25.4 cm) 10” (25.4 cm) 11.5 8.8/9.5
VBCV6638 VIV1200* VEV1200*/1500 10” (25.4 cm) 10” (25.4 cm) 11.5 8.8/9.5
VICV3698 VIV600/VIV1200* VEV900/1200* 7” (17.8 cm) 10” (25.4 cm) 4.9/7.4 7.4/4.7
VICV4298 VIV600/1200* VEV900/1200*/1500 7” (17.8 cm) 10” (25.4 cm) 4.9 7.4/4.8/5.4
VICV5498 VIV1200* VEV1200*/1500 10” (25.4 cm) 10” (25.4 cm) 8.2 5.6/6.2
VICV6698 VIV1200* VEV1200*/1500 10” (25.4 cm) 10” (25.4 cm) 9.0 6.3/7.1
DBCV3082 DIV300/440 DEV900**/1200* 7” (17.8 cm) 10” (25.4 cm) 1.7/3.2 6.6/3.9
DBCV3682 DIV300/440 DEV900**/1200* 7” (17.8 cm) 10” (25.4 cm) 1.7/3.2 6.6/3.9
DBCV4282 DIV440 DEV900**/1200* 7” (17.8 cm) 10” (25.4 cm) 3.2 6.6/3.9
DBCV4882 DIV880 DEV1200/1500 10” (25.4 cm) 10” (25.4 cm) 5.6 4.3/5.1
DICV3632 DIV440 DEV900**/1200* 7” (17.8 cm) 10” (25.4 cm) 4.0 7.5/5.2
DICV4232 DIV440 DEV900**/1200/1500 7” (17.8 cm) 10” (25.4 cm) 4.0 7.5/5.2/6.0
DICV5432 DIV880 DEV1200/1500 10” (25.4 cm) 10” (25.4 cm) 6.4 5.2/6.0
*1200 CFM interior and exterior (if applicable) ventilator should be used with all outdoor approved models and when indoor models are installed over
ranges/rangetops with gas grill.
**Must use 8” duct from canopy to ceiling – trasition to 10” duct past duct cover.
Note: Exhaust capacity based on tests with 0.1 static pressure. Without applying static pressure (some brands do not), CFM could be
greatly overstated.
UTILITY REQUIREMENTS