Viking VWH6078T Ventilation Hood User Manual


 
Proper installation/ ducting is
extremely important to ensure
maximum performance. Use a qualified
and trained installer.
DUCTING
• Check with a qualified and
trained installer or local codes
for makeup air requirements, if
any.
• Max. duct run
o For 1,200 CFM—50’ (15.2 m)
o For 1,500 CFM—75’ (22.9 m)
o Duct run length is for
general reference only; for
longer duct runs, increase
duct size and contact a
qualified and trained
installer.
o The 1,500 CFM ventilator
should be used with longer
duct runs.
o Straight runs and gradual
turns are best; for example,
each 90° elbow is equivalent
to 5 – 10 feet (1.52 – 3.05
cm) of straight run.
10” duct run for 900 – 1500
CFM
o Never use flexible duct; it
creates back pressure/air
turbulence and greatly
reduces performance.
ELECTRICAL
Hardwire direct with two-wire
with ground
120 VAC/60 Hz
PLUMBING
Not applicable
GAS
Not applicable
VWH4878T
48”W. Hood (for 41”W. grills)
VWH6078T
60”W. Hood (for 53”W. grills)
VWH3678T
36”W. Hood (for 30”W. grills)
PLANNING AND DESIGN GUIDE
VIKINGRANGE.COM • 1-888-VIKING1
RELEASED 12/1/07
©2007 VRC—INFORMATION SUBJECT TO CHANGE
OUTDOOR—VENTILATION
Built-In 18”H. Wall Hood
UTILITY
REQUIREMENTS
Installation Requirements
Model Ventilator Kits Duct Size Max. Amps*
Interior Exterior Interior Exterior Interior Exterior
VWH3678T VIV1200 VEV1200/1500 10” (25.4 cm) 10” (25.4 cm) 8.7 6.1/6.8
VWH4878T VIV1200 VEV1200/1500 10” (25.4 cm) 10” (25.4 cm) 11.5 8.8/9.5
VWH6078T VIV1200 VEV1200/1500 10” (25.4 cm) 10” (25.4 cm) 11.5 8.8/9.5
*Maximum amp rating for hoods includes recommended ventilator kit rating.