After piping has been checked for leaks, fully purge gas pipes to remove air.
GAS PRESSURES (ALL MODELS):
The gas pressure should be set at 4” W.C. (Water Column) (0.8 kPa) for natural gas and
10” W.C. (2.75 kPa) for propane gas. If incoming pressure exceeds ½ PSI (3.45 kPa), an
additional pressure regulator must be installed.
TESTING THE GAS SUPPLY PIPING SYSTEM:
When test pressures exceed ½ PSI (3.45 kPa), the fryer and its individual shutoff valve
must be disconnected from the gas supply piping system.
When test pressures are ½ PSI (3.45 kPa) or less, the fryer must be isolated from the gas
supply piping system by closing its individual shutoff valve.
Fryers with Casters:
Separate instructions for installing casters are included with the casters:
The installation shall be made with a connector that complies with the
Standard for Connectors for Movable Gas Appliances, ANSI Z21.69 or Connectors
for Moveable Gas Appliances, CAN/CGA-6.16, and a quick-disconnect device that
complies with the Standard for Quick-Disconnect Devices for Use with Gas Fuel,
ANSI z21.41 or Quick-Disconnect Devices for Use with Gas Fuel, CANI-6.9.
When installing a quick disconnect you must also install a means for limiting the
movement of the fryer. This device will prevent the gas line or quick disconnect
from being strained. The restraining device should be attached to the cutout on the
back panel. See illustration for location.