Vulcan-Hart GRC35 ML-052083 Fryer User Manual


 
– 10 –
LOCATION
The equipment area must be kept free and clear of combustible substances. Minimum clearance from
combustible construction is 6" (15 cm) from the sides and 6" (15 cm) from the back of the fryer.
Minimum clearance from noncombustible construction is 0" from the sides and 0" from the back.
At least 16" (41 cm) clearance must be between the fryer and any open-top flame units. Adequate
clearances for servicing and proper operation must be allowed. The fryer may be installed on
combustible floors.
Install the fryer in an area with sufficient air supply for combustion of the gas at the fryer burners.
Provide adequate clearance for air openings into the combustion chamber. Do not obstruct the flow of
combustion and ventilation air. Do not permit fans to blow directly on the fryer. Avoid wall-type fans
which create cross-currents within a room. Avoid open windows next to the sides or back.
INSTALLATION CODES AND STANDARDS
The fryer must be installed in accordance with:
In the United States of America:
1. State and local codes, or in the absence of local codes, with:
2. National Fuel Gas Code, ANSI-Z223.1 (latest edition), available from The American Gas
Association, Inc., 1515 Wilson Blvd., Arlington, VA 22209.
3. National Electrical Code ANSI/NFPA70 (latest edition) (if applicable).
In Canada:
1. Local codes.
2. CSA Standard C22.2 No. 3 Electrical Features of Fuel Burning Equipment (latest edition).
3. CAN/CGA-B149.1 National Fuel Gas Code (latest edition), available from The Canadian Gas
Association, 178 Rexdale Rd., Etobicoke, Ontario, Canada M9W 1R3.